CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
DEVICE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
5–39
Transient Recorder
The Transient Recorder contains waveforms captured at the same sampling rate as the
other relay data at the point of trigger. By default, data is captured for all AC current and
voltage inputs available on the relay as ordered. Transient record is generated upon
change of state of at least one of the assigned triggers: “Trigger Source”, “Trigger on
Pickup”, “Trigger on Operate”, “Trigger on Alarm”, or “Trigger on Trip”.
The number of cycles captured in a single transient record varies based on the number of
records, sample rate, and the number of selected channels. There is a fixed amount of data
storage for the Transient Recorder: the more data captured, the less the number of cycles
captured per record.
Path
:
Setpoints > Device > Transient Recorder
NUMBER OF RECORDS
Range: 1 to 16 in steps of 1
Default: 5
The selection from the range defines the desired number of records.
SAMPLES PER CYCLE
Range: 8/c, 16/c, 32/c, 64/c, 128/c
Default: 32/c
This setpoint provides a selection of samples-per-cycle for representing the waveform.
The waveform records can be viewed using the 8-series PC program.
TRIGGER MODE
Range: Overwrite, Protected
Default: Overwrite
When “Overwrite” setting is selected, the new records overwrite the old ones, meaning
the relay will always keep the newest records as per the selected number of records. In
“Protected” mode, the relay will keep the number of records corresponding to the
selected number of records, without saving further records that are beyond the selected
number of records.
TRIGGER POSITION
Range: 0 to 100% in steps of 1%
Default: 20%
This setting indicates the location of the trigger with respect to the selected length of
record. For example at 20% selected trigger position, the length of each record will be
split on 20% pre-trigger data, and 80% post-trigger data.
TRIGGER SOURCE:
Range: Off, Any FlexLogic operand
Default: Off
The trigger source can be any digital input: an operand from the list of FlexLogic
operands, a contact input, a contact output, a virtual input or output, or a remote input
or output.
TRIGGER ON ANY PICKUP
Range: On, Off
Default: Off
Selection of “On” setting enables triggering of the recorder upon pickup condition
detected by any of the protection or control elements.
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...