CHAPTER 3: INTERFACES
FRONT CONTROL PANEL INTERFACE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
3–11
Rugged and Membrane (3 PB) Front Panel LEDs
Front panel LED details:
•
Number of LEDs: 17
•
Programmability: Any FlexLogic operand
•
Reset mode: self-reset or latched
The 850 front panel provides two columns of 7 LED indicators each, and 3 LED pushbutton
indicators. The “IN-SERVICE” (LED 1) and the “PICKUP” (LED 4) indicators from the first LED
column are non-programmable LEDs. The bottom 3 LED indicators from the first column,
and the 7 LED indicators from the second LED column are fully programmable. The
indicators “TRIP” (LED 2), and “ALARM” (LED 3), are also programmable, and can be
triggered by either a selection of FlexLogic operand assigned in their own menu, or by the
operation of any protection, control or monitoring element with function selected as Trip,
Alarm, or Latched Alarm.
The RESET key is used to reset any latched LED indicator or Target Message once the
condition has been cleared (latched conditions can also be reset via the RESETTING menu).
Figure 3-10: LED numbering
Figure 3-11: Typical LED Indicator Panel
Some status indicators are common while some are feature specific which depend on the
availability in the order code. The common status indicators in the first column are
described below.
•
IN SERVICE
–
Green color = Relay powered up, passed self-test has been programmed, and
ready to serve. This LED indicates that control power is applied, all monitored
inputs, outputs, and internal systems are OK, and that the device has been
programmed.
–
Red color = Relay failed self test, has not been programmed, or out of service
•
TRIP
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
LED 9
LED 10
LED 11
LED 12
LED 13
LED 14
LED 15
LED 16
LED 17
IN SERVICE
TRIP
ALARM
PICK UP
AR ENABLED
AR IN PROGRESS
AR LOCKOUT
BKR OPEN
BKR CLOSED
LOCAL MODE
SYNCHECK OK
TEST MODE
MESSAGE
Summary of Contents for Multilin 850
Page 10: ...VIII 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 135: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 41 ...
Page 151: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 57 ...
Page 153: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 3 59 ...
Page 439: ...CHAPTER 7 MONITORING FUNCTIONS 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL 7 19 ...
Page 644: ...11 20 850 FEEDER PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 11 METERING ...