Proline Prowirl F 200 PROFIBUS PA
Commissioning
Hauser
117
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Assign simulation process variable
–
Select a process variable for
the simulation process that is
activated.
• Off
• Volume flow
• Corrected volume
flow
• Mass flow
• Flow velocity
• Temperature
• Calculated
saturated steam
pressure
• Steam quality
• Total mass flow
• Condensate mass
flow
• Energy flow
• Heat flow
difference
• Reynolds number
Off
Value process variable
One of the following options is
selected in the
Assign
simulation process variable
parameter (→ 117):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated saturated steam
pressure
• Steam quality
• Total mass flow
• Condensate mass flow
• Energy flow
• Heat flow difference
• Reynolds number
Enter the simulation value for
the selected process variable.
Depends on the
process variable
selected
0
Frequency simulation
In the
Operating mode
parameter, the
Frequency
option is selected.
Switch the simulation of the
frequency output on and off.
• Off
• On
Off
Frequency value
In the
Frequency simulation
parameter, the
On
option is
selected.
Enter the frequency value for
the simulation.
0.0 to 1
250.0 Hz
0.0 Hz
Pulse simulation
In the
Operating mode
parameter, the
Pulse
option is
selected.
Set and switch off the pulse
output simulation.
For
Fixed value
option:
Pulse width
parameter
(→ 104) defines the
pulse width of the pulses
output.
• Off
• Fixed value
• Down-counting
value
Off
Pulse value
In the
Pulse simulation
Down-counting value
option
is selected.
Enter the number of pulses for
simulation.
0 to 65
535
0
Switch output simulation
In the
Operating mode
parameter, the
Switch
option
is selected.
Switch the simulation of the
switch output on and off.
• Off
• On
Off