Diagnostics and troubleshooting
Proline Prowirl F 200 PROFIBUS PA
164
Hauser
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
494 Switch output simulation
Deactivate simulation switch output
• Calculated saturated
steam pressure
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Corrected volume flow
• Steam quality
• Temperature
• Volume flow
Measured variable status
Quality
Good
Quality substatus
Function check
Coding (hex)
0xBC to 0xBF
Status signal
C
Diagnostic behavior
Warning
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
495 Simulation diagnostic event
Deactivate simulation
–
Measured variable status
Quality
Good
Quality substatus
Ok
Coding (hex)
0x80 to 0x83
Status signal
C
Diagnostic behavior
Warning
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
497 Simulation block output
Deactivate simulation
–
Measured variable status
Quality
Good
Quality substatus
Ok
Coding (hex)
0x80 to 0x83
Status signal
C
Diagnostic behavior
Warning
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
538 Flow computer configuration incorrect
Check input value (pressure, temperature)
• Calculated saturated
steam pressure
• Density
• Energy flow
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
Measured variable status
Quality
Good
Quality substatus
Function check
Coding (hex)
0xBC to 0xBF
Status signal
S
Diagnostic behavior
Warning
Summary of Contents for Proline Prowirl F 200