Electrical connection
Proline Prowirl F 200 PROFIBUS PA
34
Hauser
7.2
Connecting the measuring device
NOTICE
Limitation of electrical safety due to incorrect connection!
‣
Have electrical connection work carried out by appropriately trained specialists only.
‣
Observe applicable federal/national installation codes and regulations.
‣
Comply with local workplace safety regulations.
‣
Always connect the protective ground cable before connecting additional cables.
‣
For use in potentially explosive atmospheres, observe the information in the device-
specific Ex documentation.
7.2.1
Connecting the compact version
Connecting the transmitter
The connection of the transmitter depends on the following order code:
"Electrical connection":
– Option
A
,
B
,
C
,
D
: terminals
– Option
I
,
M
: device plug
Connection via terminals
10 (0.4)
mm (in)
20 mm
3 mm
1.
2.
3.
4.
5.
6.
A0032239
1. Loosen the securing clamp of the connection compartment cover.
2. Unscrew the connection compartment cover.
3. Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4. Strip the cable and cable ends. In the case of stranded cables, also fit ferrules.
5. Connect cable in accordance with terminal assignment→ 31..
6.
L
WARNING
Housing degree of protection may be voided due to insufficient sealing of the
housing.
‣
Screw in the screw without using any lubricant. The threads on the cover are
coated with a dry lubricant.
Firmly tighten the cable glands.
7. Reverse the removal procedure to reassemble the transmitter.