Proline Prowirl F 200 PROFIBUS PA
Diagnostics and troubleshooting
Hauser
173
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
945 Sensor range exceeded
Check immediately process conditions
(pressure-temperature rating)
• Calculated saturated
steam pressure
• Density
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
• Volume flow
Measured variable status [from the factory]
Quality
Uncertain
Quality substatus
Process related
Coding (hex)
0x78 to 0x7B
Status signal
S
Diagnostic behavior
Warning
1)
Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
946 Vibration detected
Check installation
• Calculated saturated
steam pressure
• Density
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
• Volume flow
Measured variable status
Quality
Uncertain
Quality substatus
Process related
Coding (hex)
0x78 to 0x7B
Status signal
S
Diagnostic behavior
Warning
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
947 Vibration exceeded
Check installation
• Calculated saturated
steam pressure
• Density
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
• Volume flow
Measured variable status [from the factory]
Quality
Uncertain
Quality substatus
Process related
Coding (hex)
0x78 to 0x7B
Status signal
S
Diagnostic behavior
Alarm
1)
Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.
Summary of Contents for Proline Prowirl F 200
Page 224: ...www addresses endress com...