Proline Prowirl F 200 PROFIBUS PA
Technical data
Hauser
201
Temperature
• Saturated steam and liquids at room temperature, if T > 100 °C (212 °F):
< 1 °C (1.8 °F)
• Gas: < 1 % o.r. [K]
• Volume flow: 70 m/s (230 ft/s): 2 % o.r.
• Rise time 50 % (stirred under water, following IEC 60751): 8 s
Mass flow saturated steam
Sensor version
Mass (integrated temperature
measurement)
Mass (integrated pressure/
temperature measurement)
Process
pressure
[bar abs.]
Flow velocity
[m/s (ft/s)]
Reynolds
number
Window
Measured
value
deviation
PremiumCal
Standard
PremiumCal
Standard
> 4.76
20 to 50
(66 to 164)
Re
2
to Re
max
A1
< 1.6 %
< 1.7 %
< 1.4 %
< 1.5 %
> 3.62
10 to 70
(33 to 230)
Re
2
to Re
max
A1
< 1.9 %
< 2.0 %
< 1.7 %
< 1.8 %
In all cases not specified here, the following applies: < 5.7 %
1)
Sensor version available only for measuring devices in HART communication mode.
2)
Order code for "Calibration flow", option N "0.65% volume PremiumCal 5-point, extended turndown"
Mass flow of superheated steam/gases
Sensor version
Mass (integrated pressure/
temperature measurement)
Mass (integrated temperature
measurement) + external pressure
compensation
Process
pressure
[bar abs.]
Flow velocity
[m/s (ft/s)]
Reynolds
number
Window
Measured
value
deviation
PremiumCal
Standard
PremiumCal
Standard
< 40
All velocities Re
2
to Re
max
A1
< 1.4 %
< 1.5 %
< 1.6 %
< 1.7 %
< 120
Re
2
to Re
max
A1
< 2.3 %
< 2.4 %
< 2.5 %
< 2.6 %
In all cases not specified here, the following applies: < 6.6 %
1)
Sensor version available only for measuring devices in HART communication mode.
2)
The use of a Cerabar S is required for the measured errors listed in the following section. The measured error used to calculate the error in the
measured pressure is 0.15 %.
3)
Order code for "Calibration flow", option N "0.65% volume PremiumCal 5-point, extended turndown"
Water mass flow
Sensor version
Mass (integrated temperature measurement)
Process pressure
[bar abs.]
Flow velocity
[m/s (ft/s)]
Reynolds number
Window
Measured value deviation
PremiumCal
Standard
All pressures
All velocities
Re
2
to Re
max
A1
< 0.75 %
< 0.85 %
Re
1
to Re
2
A2
< 2.6 %
< 2.7 %
1)
Order code for "Calibration flow", option N "0.65% volume PremiumCal 5-point, extended turndown"
4)
single gas, gas mixture, air: NEL40; natural gas: ISO 12213-2 contains AGA8-DC92, AGA NX-19, ISO 12213-3 contains SGERG-88 and AGA8
Gross Method 1