Operation
Proline Prowirl F 200 PROFIBUS PA
136
Hauser
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Control Totalizer 1 to n
In the
Assign process variable
parameter, one of the
following options is selected:
• Volume flow
• Mass flow
• Corrected volume flow
• Total mass flow
• Condensate mass flow
• Energy flow
• Heat flow difference
Control totalizer value.
• Totalize
• Reset + hold
• hold
Totalize
Preset value 1 to n
In the
Assign process variable
parameter one of the following
options is selected:
• Volume flow
• Mass flow
• Corrected volume flow
• Total mass flow
• Condensate mass flow
• Energy flow
• Heat flow difference
Specify start value for totalizer. Signed floating-point
number
0 m³
Reset all totalizers
–
Reset all totalizers to 0 and
start.
• Cancel
• Reset + totalize
Cancel
*
Visibility depends on order options or device settings
11.7 Showing data logging
The
Extended HistoROM
application package must be enabled in the device (order
option) for the
Data logging
submenu to appear. This contains all the parameters for the
measured value history.
Data logging is also available via:
Plant Asset Management Tool FieldCare → 57.
Function range
• A total of 1000 measured values can be stored
• 4 logging channels
• Adjustable logging interval for data logging
• Display of the measured value trend for each logging channel in the form of a chart
0
/ ../XXXXXXXX
175.77
40.69 l/h
-100s
A0034352
• x-axis: depending on the number of channels selected displays 250 to 1000 measured
values of a process variable.
• y-axis: displays the approximate measured value span and constantly adapts this to the
ongoing measurement.
If the length of the logging interval or the assignment of the process variables to the
channels is changed, the content of the data logging is deleted.