Proline Prowirl F 200 PROFIBUS PA
Commissioning
Hauser
101
Inlet run
Mating pipe diameter
Installation factor
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Inlet configuration
The
inlet run correction
feature:
• Is a standard feature and
can only be used in Prowirl F
200.
• Can be used for the
following pressure ratings
and nominal diameters:
DN 15 to 150 (1 to 6")
– EN (DIN)
– ASME B16.5, Sch. 40/80
Select inlet configuration.
• Off
• Single elbow
• Double elbow
• Double elbow 3D
• Reduction
Off
Inlet run
The
inlet run correction
feature:
• Is a standard feature and
can only be used in Prowirl F
200.
• Can be used for the
following pressure ratings
and nominal diameters:
DN 15 to 150 (1 to 6")
– EN (DIN)
– ASME B16.5, Sch. 40/80
Define length of the straight
inlet run.
Dependency
The unit is taken from the
Length unit
parameter
0 to 20 m
0 m
Mating pipe diameter
–
Enter diameter of mating pipe
to enable diameter mismatch
correction.
Detailed information on
diameter mismatch correction:
→ 102
Dependency
The unit is taken from the
Length unit
parameter.
0 to 1 m (0 to 3 ft)
Input value = 0:
Diameter mismatch
correction is disabled.
Country-specific:
• 0 m
• 0 ft
Installation factor
–
Enter factor to adjust for
installation conditions.
Positive floating-
point number
1.0
Inlet run correction
The
Inlet Run Correction
feature of Hauser's measuring device presents an
economic method for shortening the inlet run and does not generate any additional
pressure loss. The typical systematic errors caused by the pipe component in question are
corrected.