Proline Prowirl F 200 PROFIBUS PA
Diagnostics and troubleshooting
Hauser
167
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
829 Ambient temperature too high
Reduce ambient temperature of pre-
amplifier
• Calculated saturated
steam pressure
• Density
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
• Temperature
• Volume flow
Measured variable status [from the factory]
Quality
Uncertain
Quality substatus
Process related
Coding (hex)
0x78 to 0x7B
Status signal
S
Diagnostic behavior
Warning
1)
Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
832 Electronic temperature too high
Reduce ambient temperature
• Calculated saturated
steam pressure
• Density
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
• Temperature
• Volume flow
Measured variable status [from the factory]
Quality
Uncertain
Quality substatus
Process related
Coding (hex)
0x78 to 0x7B
Status signal
S
Diagnostic behavior
Warning
1)
Diagnostic behavior can be changed. This causes the overall status of the measured variable to change.