Proline Prowirl F 200 PROFIBUS PA
Diagnostics and troubleshooting
Hauser
165
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
539 Flow computer configuration incorrect
1. Check input value (pressure,
temperature)
2. Check allowed values of the medium
properties
• Calculated saturated
steam pressure
• Density
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
• Volume flow
Measured variable status
Quality
Bad
Quality substatus
Function check
Coding (hex)
0x3C to 0x3F
Status signal
S
Diagnostic behavior
Alarm
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
540 Flow computer configuration incorrect
Check entered reference value using the
document Operating Instructions
• Calculated saturated
steam pressure
• Density
• Energy flow
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
Measured variable status
Quality
Good
Quality substatus
Function check
Coding (hex)
0xBC to 0xBF
Status signal
S
Diagnostic behavior
Warning
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
570 Inverted delta heat
Check configuration of mounting location
(parameter Installation direction)
Heat flow difference
Measured variable status
Quality
Bad
Quality substatus
Function check
Coding (hex)
0x3C to 0x3F
Status signal
F
Diagnostic behavior
Alarm