Proline Prowirl F 200 PROFIBUS PA
Commissioning
Hauser
107
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Failure mode
In the
Operating mode
Frequency
option is selected,
and one of the following
options is selected in the
Assign frequency output
parameter (→ 105):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated saturated steam
pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
Define output behavior in
alarm condition.
• Actual value
• Defined value
• 0 Hz
0 Hz
Failure frequency
In the
Operating mode
Frequency
option is selected,
and one of the following
options is selected in the
Assign frequency output
parameter (→ 105):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated saturated steam
pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
Enter frequency output value
in alarm condition.
0.0 to 1
250.0 Hz
0.0 Hz
Invert output signal
–
Invert the output signal.
• No
• Yes
No
*
Visibility depends on order options or device settings
Configuring the switch output
Navigation
"Setup" menu → Pulse/frequency/switch output
Pulse/frequency/switch output
Switch output function
Assign diagnostic behavior
Assign limit
Assign flow direction check