Technical data
Proline Prowirl F 200 PROFIBUS PA
198
Hauser
Supply voltage
Transmitter
An external power supply is required for each output.
The following supply voltage values apply for the outputs available:
Supply voltage for a compact version without a local display
Order code for "Output; input"
Minimum
terminal voltage
Maximum
terminal voltage
Option
G
: PROFIBUS PA, pulse/frequency/
switch output
≥ DC 9 V
DC 32 V
1)
In event of external supply voltage of the PROFIBUS DP/PA coupler
2)
The minimum terminal voltage increases if local operation is used: see the following table
Increase in minimum terminal voltage
Order code for "Display; operation"
Increase in minimum
terminal voltage
Option
C
:
Local operation SD02
+ DC 1 V
Option
E
:
Local operation SD03 with lighting
(
backlighting
not used)
+ DC 1 V
Option
E
:
Local operation SD03 with lighting
(
backlighting
used)
+ DC 3 V
Power consumption
Transmitter
Order code for "Output; input"
Maximum power consumption
Option
G
: PROFIBUS PA, pulse/frequency/
switch output
• Operation with output 1: 512 mW
• Operation with output 1 and 2: 2
512 mW
Current consumption
PROFIBUS PA
15 mA
Power supply failure
• Totalizers stop at the last value measured.
• Configuration is retained in the device memory (HistoROM).
• Error messages (incl. total operated hours) are stored.
Electrical connection
Potential equalization
Terminals
• For device version without integrated overvoltage protection: plug-in spring terminals
for wire cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
• For device version with integrated overvoltage protection: screw terminals for wire cross-
sections 0.2 to 2.5 mm
2
(24 to 14 AWG)