Proline Prowirl F 200 PROFIBUS PA
Commissioning
Hauser
105
Minimum frequency value
Maximum frequency value
Measuring value at minimum
frequency
Measuring value at maximum
frequency
Failure mode
Failure frequency
Invert output signal
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Assign frequency output
The
Frequency
option is
selected in the
Operating
mode
parameter.
Select process variable for
frequency output.
• Off
• Volume flow
• Corrected volume
flow
• Mass flow
• Flow velocity
• Temperature
• Calculated
saturated steam
pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow
difference
Off
Minimum frequency value
In the
Operating mode
parameter, the
Frequency
option is selected, and one of
the following options is
selected in the
Assign
frequency output
parameter
(→ 105):
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Pressure
• Calculated saturated steam
pressure
• Steam quality
• Total mass flow
• Energy flow
• Heat flow difference
Enter minimum frequency.
0 to 1
000 Hz
0 Hz