Proline Prowirl F 200 PROFIBUS PA
Technical data
Hauser
197
Local display
Plain text display
With information on cause and remedial measures
Backlight
Additionally for device version with SD03 local display: red lighting indicates a
device error.
Status signal as per NAMUR recommendation NE 107
Interface/protocol
• Via digital communication:
PROFIBUS PA
• Via service interface
CDI service interface
Plain text display
With information on cause and remedial measures
Low flow cut off
The switch points for low flow cut off are preset and can be configured.
Galvanic isolation
All inputs and outputs are galvanically isolated from one another.
Protocol-specific data
Manufacturer ID
0x11
Ident number
0x1564
Profile version
3.02
Device description files (GSD,
DTM, DD)
Information and files under:
•
•
www.profibus.org
Supported functions
• Identification & Maintenance
Simple device identification via control system and nameplate
• PROFIBUS upload/download
Reading and writing parameters is up to ten times faster with PROFIBUS
upload/download
• Condensed status
Simplest and self-explanatory diagnostic information by categorizing
diagnostic messages that occur
Configuration of the device
address
• DIP switches on the I/O electronics module
• Local display
• Via operating tools (e. g. FieldCare)
System integration
For information on system integration, see .→ 62
• Cyclic data transmission
• Block model
• Description of the modules
16.5 Power supply
Terminal assignment
Pin assignment, device plug