Commissioning
Proline Prowirl F 200 PROFIBUS PA
100
Hauser
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Fixed process pressure
The following conditions are
met:
• Order code for "Sensor
version",
Option "Mass flow
(integrated temperature
measurement)"
• In the
External value
parameter (→ 99) the
Pressure
option is not
selected.
Enter fixed value for process
pressure.
Dependency
The unit is taken from the
Pressure unit
parameter.
For detailed information
on the calculation of the
measured variables with
steam: → 125
For detailed information
on setting the parameter
in steam applications,
see the Special
Documentation for the
Wet Steam Detection
and
Wet Steam
Measurement
application package
0 to 250 bar abs.
0 bar abs.
Steam quality
The following conditions are
met:
• Order code for "Application
package":
– Option ES "Wet steam
detection"
– Option EU "Wet steam
measurement"
• The
Steam
option is
selected in the
Select
medium
parameter
parameter.
The software options
currently enabled are
displayed in the
Software option
overview
parameter.
Select compensation mode for
steam quality.
For detailed information
on setting the parameter
in steam applications,
see the Special
Documentation for the
Wet Steam Detection
and
Wet Steam
Measurement
application package
• Fixed value
• Calculated value
Fixed value
Steam quality value
The following conditions are
met:
• The
Steam
option is
selected in the
Select
medium
parameter
parameter.
• The
Fixed value
option is
selected in the
Steam
quality
parameter
parameter.
Enter fixed value for steam
quality.
For detailed information
on setting the parameter
in steam applications,
see the Special
Documentation for the
Wet Steam Detection
and
Wet Steam
Measurement
application package
0 to 100 %
100 %
10.5.3 Carrying out a sensor adjustment
The
Sensor adjustment
submenu contains parameters that pertain to the functionality of
the sensor.
Navigation
"Setup" menu → Advanced setup → Sensor adjustment
‣
Sensor adjustment
Inlet configuration