Diagnostics and troubleshooting
Proline Prowirl F 200 PROFIBUS PA
162
Hauser
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
453 Flow override
Deactivate flow override
• Calculated saturated
steam pressure
• Density
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
• Temperature
• Volume flow
Measured variable status
Quality
Good
Quality substatus
Function check
Coding (hex)
0xBC to 0xBF
Status signal
C
Diagnostic behavior
Warning
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
482 FB not Auto/Cas
Set Block in AUTO mode
–
Measured variable status
Quality
Good
Quality substatus
Ok
Coding (hex)
0x80 to 0x83
Status signal
F
Diagnostic behavior
Alarm
Diagnostic information
Remedy instructions
Influenced measured
variables
No.
Short text
484 Simulation failure mode
Deactivate simulation
• Calculated saturated
steam pressure
• Density
• Energy flow
• Flow velocity
• Heat flow difference
• Low flow cut off
• Mass flow
• Total mass flow
• Switch output status
• Pressure
• Reynolds number
• Specific volume
• Corrected volume flow
• Steam quality
• Degrees of superheat
• Temperature
• Volume flow
Measured variable status
Quality
Bad
Quality substatus
Function check
Coding (hex)
0x3C to 0x3F
Status signal
C
Diagnostic behavior
Alarm