Proline Prowirl F 200 PROFIBUS PA
Commissioning
Hauser
87
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Calorific value
The following conditions are
met:
• Selected medium:
– In the
Select gas type
parameter, the
User-
specific gas
option is
selected.
Or
– In the
Select liquid type
parameter, the
User-
specific liquid
option is
selected.
• In the
Enthalpy type
parameter, the
Calorific
value
option is selected.
• In the
Calorific value type
parameter, the
Gross
calorific value volume
option or
Gross calorific
value mass
option is
selected.
Enter gross calorific value to
calculate the energy flow.
Positive floating-
point number
50
000 kJ/kg
Z-factor
In the
Select gas type
parameter, the
User-specific
gas
option is selected.
Enter real gas constant Z for
gas under operation
conditions.
0.1 to 2.0
1
Dynamic viscosity (Gases)
The following conditions are
met:
• Order code for "Sensor
version",
– Option "Volume"
or
– Option "Volume high
temperature"
• The
Gas
option or the
Steam
option is selected in
the
Select medium
parameter.
or
• The
User-specific gas
option is selected in the
Select gas type
parameter.
Enter fixed value for dynamic
viscosity for a gas/steam.
Dependency
The unit is taken from the
Dynamic viscosity unit
parameter.
Positive floating-
point number
0.015 cP
Dynamic viscosity (Liquids)
The following conditions are
met:
• Order code for "Sensor
version",
– Option "Volume"
or
– Option "Volume high
temperature"
• The
Liquid
option is
selected in the
Select
medium
parameter
parameter.
or
• The
User-specific liquid
option is selected in the
Select liquid type
parameter.
Enter fixed value for dynamic
viscosity for a liquid.
Dependency
The unit is taken from the
Dynamic viscosity unit
parameter.
Positive floating-
point number
1 cP
Configuring the gas composition
In the
Gas composition
submenu the gas composition for the measuring application can
be set.