background image

Wiring Diagram

Input Specification

Aspect & Panel Cutout Dimension

ME0205K071126

Suffix Code Structure

Unit :   mm

Before you use, read safety precautions carefully, and use this product properly. The
precautions described in this manual contain important contents related with safety; therefore,
please follow the instructions accordingly. The precautions are composed of DANGER,
WARNING and CAUTION.

There is a danger of occurring electric shock in the input/output terminals so please never let
your body or conductive substance is touched.

1. This product does not contain an electric switch or fuse, so the user needs to install a

separate electric switch or fuse externally. (Fuse rating: 250V 0.5A)

2. To prevent defection or malfunction of this product, apply a proper power voltage in

accordance with the rating.

3. To prevent electric shock or malfunction of product, do not supply the power until the wiring

is completed.

4. Do not decompose, modify, revise or repair this product. This may be a cause of

malfunction, electric shock or fire.

5. Reassemble this product while the power is OFF. Otherwise, it may be a cause of

malfunction or electric shock.

6. If you use the product with methods other than specified by the manufacturer, there may be

bodily injuries or property damages.

7. There is a possibility of occurring electric shock so please use this product after installing it

onto a panel while it is operating.

1. The contents of this manual may be changed without prior notification.
2. Before using the product you purchased, make sure that it is exactly what you ordered.
3. Make sure that there is no damage or abnormality of the product during the delivery.
4. Do not use this product at any place with occurring corrosive (especially noxious gas or

ammonia) or flammable gas.

5. Do not use this product at any place with direct vibration or impact.
6. Do not use this product at any place with liquid, oil, medical substances, dust, salt or iron

contents. (Use at Pollution level 1 or 2)

7. Do not polish this product with substances such as alcohol or benzene. (Use neutral

detergent.)

8. Do not use this product at any place with a large inductive difficulty or occurring static

electricity or magnetic noise.

9. Do not use this product at any place with possible thermal accumulation due to direct

sunlight or heat radiation.

10. Install this product at place under 2,000m in altitude.
11. When the product gets wet, the inspection is essential because there is danger of an

electric leakage or fire.

12. If there is excessive noise from the power supply, using insulating transformer and noise

filter is recommended.  

13. The noise filter must be attached to a panel which is already connected to a ground and the

wire between the filter output side and power supply terminal must be short as possible.

14. If twisting the power cables closely together then it is effective against noise.
15. Do not connect anything to the unused terminals.
16. After checking the polarity of terminal, connect wires at the correct position.
17. When this product is connected onto a panel, use a circuit breaker or switch approved with

IEC947-1 or IEC947-3.

18. Install a circuit breaker or switch at near place for convenient use.
19. Write down on a label that if the circuit breaker or switch is operating then the power will be

disconnected since the circuit breaker or switch is installed.

20. For the continuous and safe use of this product, the periodical maintenance is

recommended.

21. Some parts of this product have limited life span, and others are changed by their usage.
22. The warranty period for this product including parts is one year if this product is properly used.

Safety information

WARNING

CAUTION

DANGER

Power Supply

Power Consumption

Voltage for Sensor

Measurement

Accuracy

Measurement Range

Prescale

Input Signal

Max. Displayable Digits

Display Method

Display Cycle

Hysteresis

Functions

Output Types

Insulation Resistance

Noise Immunity

Dielectric Strength

Durability

Malfunction

Output

100 ~ 240 V a.c (50 - 60 Hz), 24 ~ 60 V (a.c / d.c)

Approx. 9.5 V A (220 V a.c 60 Hz), Approx. 5 W(24 V d.c)

12 V d.c 

10 % 120 

Mode F1 : FS 

0.05 rdg 

1 dig

Mode F2, F3, F4, F5, F6: FS 

0.01 % rdg 

1 dig

Mode F1 : 0.0003 ~ 10

Mode F2 : 0.0003 ~ 1000

Mode F3, F4, F5, F6 : 0.001s-3,200 s

Mode F7, F8, F9 : 0-4

10

9

Count

Non-Contact Input :

Max. 10 

(ON voltage: 4.5 V - 24 V, OFF voltage: 0 - 1.0 V)

Contact Input : 

Max. 30 Hz 

(12 V DC, able to switch the current of 2 mA sufficiently)

5 digits (0 ~ 99999)

7 Segment (Font size(W)83 mm  x (H)14 mm)

0.05/0.5/1/2/4/8 sec  

0 ~ 9999 (applicable only for output type)

Auto Zero Time Setting Function

Display Cycle Setting Function

Time Unit Selection Function

Parameter Lock Function

Remote/Local Conversion Function  

(applicable only for communication output type)

Current Output Range Selection Function  

(applicable only for current output type)

Max. Min. Peak Value 10 Steps Memory Function

Start Compensation Timer Function

Electricity Failure Compensation (applicable only for F9)

Comparative Output Function (HH, H, GO, L, LL)

Transistor Output (NPN/PNP Open Collector Output):

Comparative Alarm Output

Relay Output (HH, H, GO, L, LL)

PV Transfer Output (4 - 20 

d.c): Displayed Value

Output

RS485 Communication Output : 32 channels : Displayed

Value Output, PC Setting Function) 

BCD Dynamic Displayed Value Output Function

Low Speed serial Output

Above 10 

(at 500 V DC mega) Between electrically 

chargeable part and non-electrically chargeable part

By noise simulator, square-shaped wave noise  

(pulse width 1 

2000 V

2000 V AC 50 Hz for 1 minute

(between AC power terminal and case,  

between AC terminal and measurement input terminal)

10 - 55 Hz double amplitude width 0.75 mm  

in each X

Y

Z direction for 2 hours

10 - 55 Hz double amplitude width 0. 5 mm 

in each X

Y

Z direction for 10 minutes

Ratings

HEAD OFFICE 

1381-3, Juan-Dong, Nam-Gu Incheon, Korea

TEL: (82-32)876-4697  FAX : (82-32)876-4696

MAIN PRODUCTS
- DIGITAL : Temperature Controller, Counter, Timer,Speedmeter, 

Tachometer, Panel Meter, Recorder

- SENSOR : Proximity Sensor/Photo Electric Sensor, 

Rotary Encoder, Optical Fiber Sensor,   
Pressure Sensor

- ANALOG : Timer, Temperature Controller

Multi Pulse Meter

RP3

We appreciate you for purchasing HanYoung NUX Co.,Ltd
product. Before using the product you have purchased,
check to make sure that it is exactly what you ordered. Then,
please use it following the instructions below.

INSTRUCTION MANUAL

Input Type Setting

Caution when selecting Sensor Type

Multi Pulse Meter

DIN Size: 96 x 48 x 105.6 

5 digits 1 stage

100 - 240V a.c (50 - 60 

)

24 - 60 V a.c / d.c

Main output

Only Display

Relay 3 stages Output

Relay 5 stages Output

NPN Open Collector 5 Stages Output

NPN Open Collector 

5 Stages Output

NPN Open Collector 5 

Stages Output 

NPN Open Collector 5 

Stages Output

Subsidiary output

-

-

-

BCD Output

4 - 20 

Current 

Output

RS-
485 communication

Low Speed Serial

-

Model Name

Suffix code

Description

RP3

Durability

Malfunction

Operating Ambient 

Temperature

Storage Temperature

Operating Ambient

Humidity

Weight

Shock 

Resis

-tance

300 m/s

2

(approx. 30G) in each X Y Z direction for 3times

100 m/s

2

(approx. 10G) in each X Y Z direction for 3times

-10 ~ +60 

(without condensation)

-20 ~ +60 

(without condensation)

35 ~ 85 % RH

Approx. 220 g

Input Specification

The max input frequency is 10 

when ON/OFF time is

higher than the minimum 50 

At this time, it can be accurately measured if the duty rate

of the input pulse is 50 %.

Above 50

Above 50    

Before connecting the sensor, if the input specification is not selected

properly, the desired measure value can not be obtained.

Example of sensor type setting

- Normal open (NPN NO)

- Normal close (NPN NC) 

Indicator [RP3 - 5A(D)N]

Contact output [RP3 - 5A(D)2]

Example : Wiring with 
                 Proximate Sensor

Contact output [RP3 - 5A(D)1]

NPN Open Collector  + BCD Output  [RP3-5A(D)3]

NPN Open Col Current Output [RP3-5A(D)4]

Subsidiary Output

NPN Open Col RS-485 Communication [RP3-5A(D)5]

NPN Open Col Low Speed Serial [RP3-5A(D)6]

: NPN Normal Open

: NPN Normal Close

Main Circuit

:  PNP Normal Open 

:  PNP  Normal Close 

Main Circuit

: Contact Input Normal Open

Main Circuit

(a Contact)

Vibration 

Resistance

Output Specification

Contact Output

Max. contact capacity : 1250 V A (a.c), 150 W (d.c)

Contact capacity : 5A 250 V a.c, 5 A 30 V d.c

Life : Electrical life - Around Fifty thousand (3A 250 V a.c)

Mechanical life - Around Ten million (Twenty times opens and closes   

per minute)

Reviews: