0-30 Unit for User-defined Readout
Option:
Function:
It is possible to program a value to
be shown in the display of the LCP.
The value has a linear, squared, or
cubed relation to speed. This
relation depends on the unit
selected (see
). The actual
calculated value can be read in
parameter 16-09 Custom Readout
and/or shown in the display by
selecting
[16-09] Custom Readout
in
parameter 0-20 Display Line 1.1
Small
to
parameter 0-24 Display Line
3 Large
.
[0]
None
[1]
*
%
[5]
PPM
[10]
1/min
[11]
rpm
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m³/s
[24]
m³/min
[25]
m³/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[80]
kW
[120]
GPM
[121]
gal/s
[122]
gal/min
[123]
gal/h
[124]
CFM
[125]
ft³/s
[126]
ft³/min
[127]
ft³/h
[130]
lb/s
[131]
lb/min
[132]
lb/h
[140]
ft/s
0-30 Unit for User-defined Readout
Option:
Function:
[141]
ft/min
[145]
ft
[160]
°F
[170]
psi
[171]
lb/in²
[172]
in WG
[173]
ft WG
[180]
HP
0-31 Min Value of User-defined Readout
Range:
Function:
0 Custom-
ReadoutUni
t
*
[ -999999.99 -
par. 0-32
CustomRea-
doutUnit]
This parameter sets the minimum
value of the custom-defined
readout (occurs at 0 speed). Only
possible to set different from 0
when selecting a linear unit in
parameter 0-30 Unit for User-defined
Readout
. For quadratic and cubic
units, the minimum value is 0.
0-32 Max Value of User-defined Readout
Range:
Function:
100
Custom-
ReadoutUni
t
*
[ par. 0-31 -
999999.99
CustomRea-
doutUnit]
This parameter sets the maximum
value to be shown when the speed
of the motor has reached the set
value for
parameter 4-13 Motor
Speed High Limit [RPM]
or
parameter 4-14 Motor Speed High
Limit [Hz]
(depends on setting in
parameter 0-02 Motor Speed Unit
).
0-37 Display Text 1
Range:
Function:
0
*
[0 - 25]
Enter a text which can be viewed in
the graphical display by selecting
[37] Display Text 1
in
•
Parameter 0-20 Display Line
1.1 Small
,
•
Parameter 0-21 Display Line
1.2 Small
,
•
Parameter 0-22 Display Line
1.3 Small
,
•
Parameter 0-23 Display Line
2 Large
, or
•
Parameter 0-24 Display Line
3 Large
.
0-38 Display Text 2
Range:
Function:
0
*
[0 - 25]
Enter a text which can be viewed in
the graphical display by selecting
[38] Display Text 2
in
Parameter Descriptions
VLT® AutomationDrive FC 361
30
Danfoss A/S © 03/2019 All rights reserved.
MG06J202
4
4