9-63 Actual Baud Rate
Option:
Function:
[7]
3000 kbit/s
[8]
6000 kbit/s
[9]
12000 kbit/s
[10]
31,25 kbit/s
[11]
45,45 kbit/s
[255]
*
No baudrate
found
9-64 Device Identification
Range:
Function:
0
*
[0 - 0 ]
Device identification parameter.
9-65 Profile Number
Range:
Function:
0
*
[0 - 0 ]
This parameter contains the profile
identification. Byte 1 contains the
profile number and byte 2 the
version number of the profile.
9-67 Control Word 1
Range:
Function:
0
*
[0 - 65535 ]
This parameter accepts the control
word from a master class 2 in the
same format as PCD 1.
9-68 Status Word 1
Range:
Function:
0
*
[0 - 65535 ]
This parameter delivers the status
word for a master class 2 in the
same format as PCD 2.
9-70 Programming Set-up
This parameter is unique for LCP and fieldbus. See
parameter 0-11 Programming Set-up
.
Option:
Function:
Select the set-up to edit.
[0]
Factory setup
Uses default data. This option can
be used as a data source to return
the other set-ups to a known state.
[1]
Set-up 1
Edits set-up 1.
[2]
Set-up 2
Edits set-up 2.
[3]
Set-up 3
Edits set-up 3.
[4]
Set-up 4
Edits set-up 4.
[9]
*
Active Set-up
Follows the active set-up selected
in
parameter 0-10 Active Set-up
.
9-71 Profibus Save Data Values
Option:
Function:
Parameter values changed via
PROFINET are not automatically
stored in the non-volatile memory.
Use this parameter to activate a
function that stores parameter
values in the EEPROM non-volatile
memory, so changed parameter
values are retained at power-down.
[0]
*
Off
Deactivate the non-volatile storage
function.
[1]
Store all
setups
Store all parameter values for all
set-ups in the non-volatile memory.
When all parameter values have
been stored, the selection returns
to
[0] Off
.
[2]
Store all
setups
Store all parameter values for all
set-ups in the non-volatile memory.
When all parameter values have
been stored, the selection returns
to
[0] Off
.
9-72 ProfibusDriveReset
Option:
Function:
[0]
*
No action
[1]
Power-on
reset
Reset frequency converter upon
power-up, as for power cycle.
[2]
Power-on
reset prep
Prepare for resetting frequency
converter upon power-up.
[3]
Comm option
reset
Reset the PROFINET option only,
the PROFINET option goes through
a power-up sequence.
When reset, the frequency
converter disappears from the
fieldbus, which may cause a
communication error from the
master.
9-75 DO Identification
Range:
Function:
0
*
[0 - 65535 ]
Provides information about the DO
(Drive Object).
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
Range:
Function:
0
*
[0 - 9999 ]
This parameter shows a list of all
the defined frequency converter
parameters available for PROFINET.
Parameter Descriptions
VLT® AutomationDrive FC 361
110
Danfoss A/S © 03/2019 All rights reserved.
MG06J202