5-40 Function Relay
Option:
Function:
to prepare switching the frequency
converter in open loop in an
emergency case.
[40]
Out of ref
range
Active when the actual speed is
outside settings in
parameter 4-52 Warning Speed Low
to
parameter 4-55 Warning Reference
High
.
[41]
Below
reference, low
Active when actual speed is below
speed reference setting.
[42]
Above ref,
high
Active when actual speed is above
speed reference setting.
[43]
Extended PID
Limit
[45]
Bus ctrl.
Controls digital output/relay via
bus. The state of the output is set
in
parameter 5-90 Digital & Relay Bus
. The output state is retained
in the event of a bus timeout.
[46]
Bus ctrl, 1 if
timeout
Controls output via bus. The state
of the output is set in
parameter 5-90 Digital & Relay Bus
Control
. If a bus timeout occurs, the
output state is set high (on).
[47]
Bus ctrl, 0 if
timeout
Controls output via bus. The state
of the output is set in
parameter 5-90 Digital & Relay Bus
Control
. If a bus timeout occurs, the
output state is set low (Off).
[59]
Remote,enable
,no TW
[60]
Comparator 0
See
parameter group 13-1*
Comparators
. If comparator 0 in SLC
is true, the output goes high.
Otherwise, it is low.
[61]
Comparator 1
See
parameter group 13-1*
Comparators
. If comparator 1 in SLC
is true, the output goes high.
Otherwise, it is low.
[62]
Comparator 2
See
parameter group 13-1*
Comparators
. If comparator 2 in SLC
is true, the output goes high.
Otherwise, it is low.
[63]
Comparator 3
See
parameter group 13-1*
Comparators
. If comparator 3 in SLC
is true, the output goes high.
Otherwise, it is low.
[64]
Comparator 4
See
parameter group 13-1*
Comparators
. If comparator 4 in SLC
5-40 Function Relay
Option:
Function:
is true, the output goes high.
Otherwise, it is low.
[65]
Comparator 5
See
parameter group 13-1*
Comparators
. If comparator 5 in SLC
is true, the output goes high.
Otherwise, it is low.
[70]
Logic rule 0
See
parameter group 13-4* Smart
Logic Control
. If logic rule 0 in SLC is
true, the output goes high.
Otherwise, it is low.
[71]
Logic rule 1
See
parameter group 13-4* Smart
Logic Control
. If logic rule 1 in SLC is
true, the output goes high.
Otherwise, it is low.
[72]
Logic rule 2
See
parameter group 13-4* Smart
Logic Control
. If logic rule 2 in SLC is
true, the output goes high.
Otherwise, it is low.
[73]
Logic rule 3
See
parameter group 13-4* Smart
Logic Control
. If logic rule 3 in SLC is
true, the output goes high.
Otherwise, it is low.
[74]
Logic rule 4
See
parameter group 13-4* Smart
Logic Control
. If logic rule 4 in SLC is
true, the output goes high.
Otherwise, it is low.
[75]
Logic rule 5
See
parameter group 13-4* Smart
Logic Control
. If logic rule 5 in SLC is
true, the output goes high.
Otherwise, it is low.
[80]
SL digital
output A
See
parameter 13-52 SL Controller
Action
. Output A is low on smart
logic action
[32]
. Output A is high
on smart logic action
[38]
.
[81]
SL digital
output B
See
parameter 13-52 SL Controller
Action
. Output B is low on smart
logic action
[33]
. Output B is high
on smart logic action
[39]
.
[82]
SL digital
output C
See
parameter 13-52 SL Controller
Action
. Output C is low on smart
logic action
[34]
. Output C is high
on smart logic action
[40]
.
[83]
SL digital
output D
See
parameter 13-52 SL Controller
Action
. Output D is low on smart
logic action
[35]
. Output D is high
on smart logic action
[41]
.
[84]
SL digital
output E
See
parameter 13-52 SL Controller
Action
. Output E is low on smart
logic action
[36]
. Output E is high
on smart logic action
[42]
.
Parameter Descriptions
VLT® AutomationDrive FC 361
74
Danfoss A/S © 03/2019 All rights reserved.
MG06J202
4
4