9-27 Parameter Edit
Option:
Function:
Parameters can be edited via
PROFIBUS, the standard RS485
interface, or the LCP.
[0]
Disabled
Disable editing via PROFIBUS.
[1]
*
Enabled
Enable editing via PROFIBUS.
9-28 Process Control
Option:
Function:
Process control (setting of control
word, speed reference, and process
data) is possible via either
PROFINET or standard fieldbus, but
not both simultaneously. Local
control is always possible via the
LCP. Control via process control is
possible via either terminals or
fieldbus depending on the settings
in
parameter 8-50 Coasting Select
to
parameter 8-58 Profidrive OFF3
Select
.
[0]
Disable
Disable process control via
PROFINET and enable process
control via standard fieldbus or
PROFINET IO supervisor.
[1]
*
Enable cyclic
master
Enable process control via IO
controller and disable process
control via standard fieldbus or
PROFINET IO supervisor.
9-44 Fault Message Counter
Range:
Function:
0
*
[0 - 65535 ]
This parameter shows the number
of error events stored in
and
. The
maximum buffer capacity is eight
error events. The buffer and counter
are set to 0 upon reset or power-
up.
9-45 Fault Code
Range:
Function:
0
*
[0 - 0 ]
This buffer contains the alarm word
for all alarms and warnings that
have occurred since last reset or
power-up. The maximum buffer
capacity is 8 error events.
9-47 Fault Number
Range:
Function:
0
*
[0 - 0 ]
This buffer contains the alarm
number (for example, 2 for live zero
error, 4 for mains phase loss) for all
alarms and warnings that have
occurred since last reset or power-
up. The maximum buffer capacity is
8 error events.
9-52 Fault Situation Counter
Range:
Function:
0
*
[0 - 1000 ]
This parameter shows the number
of error events that have occurred
since last reset or power-up.
9-53 Profibus Warning Word
Read only
Range:
Function:
0
*
[0 - 65535 ]
This parameter shows PROFINET
communication warnings.
Bit
Condition when bit is active
0
Connection with IO controller is not OK.
1
Reserved for status of connection with second IO
controller.
2
Not used.
3
Clear data command received.
4
Actual value is not updated.
5
No link on both ports.
6
Not used.
7
Initializing of PROFINET is not OK.
8
Frequency converter is tripped.
9
Internal CAN error.
10
Wrong configuration data from IO controller.
11
Not used.
12
Internal error occurred.
13
Not configured.
14
Timeout active.
15
Warning 34 active.
Table 4.17 PROFINET Communication Warnings
This parameter shows the actual PROFIBUS baud rate. The
PROFIBUS master automatically sets the baud rate.
9-63 Actual Baud Rate
Option:
Function:
[0]
9,6 kbit/s
[1]
19,2 kbit/s
[2]
93,75 kbit/s
[3]
187,5 kbit/s
[4]
500 kbit/s
[6]
1500 kbit/s
Parameter Descriptions
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
109
4
4