5-42 Off Delay, Relay
Array[20]
Range:
Function:
0.01 s
*
[0.01 - 600 s] Enter the delay of the relay cutout
time. Select 1 of 2 internal
mechanical relays in an array
function. See
parameter 5-40 Function Relay
for
details. If the selected event
condition changes before a delay
timer expires, the relay output is
unaffected.
Selected
Event
Relay
output
On Delay
P 5-41
Off Delay
P 5-42
130BA172.10
Illustration 4.27 Off Delay, Relay
If the selected event condition changes before the on
delay or off delay timer expires, the relay output is
unaffected.
4.6.4 5-5* Pulse Input
The pulse input parameters are used to define an
appropriate window for the impulse reference area by
configuring the scaling and filter settings for the pulse
inputs. Input terminals 29 or 33 act as frequency reference
inputs. Set terminal 29 (
parameter 5-13 Terminal 29 Digital
Input
) or terminal 33 (
parameter 5-15 Terminal 33 Digital
Input
) to
[32] Pulse input
. If terminal 29 is used as an input,
set
parameter 5-01 Terminal 27 Mode
to
[0] Input
.
130BA076.10
(RPM)
Ref.
Low freq.
P 5-50/
P 5-55
Input
(Hz)
High
ref.
value
P 5-53/
p 5-58
High freq.
P 5-51/
P 5-56
Low
ref.
value
P 5-52/
p 5-57
Illustration 4.28 Pulse Input
5-50 Term. 29 Low Frequency
Range:
Function:
100 Hz
*
[0 - 110000
Hz]
Enter the low frequency limit
corresponding to the low motor
shaft speed (that is low reference
value) in
. Refer to
.
5-51 Term. 29 High Frequency
Range:
Function:
Size
related
*
[0 - 110000
Hz]
Enter the high frequency limit
corresponding to the high motor
shaft speed (that is high reference
value) in
parameter 5-53 Term. 29
High Ref./Feedb. Value
.
5-52 Term. 29 Low Ref./Feedb. Value
Range:
Function:
0 Referen-
ceFeedback
Unit
*
[-999999.999
- 999999.999
Reference-
FeedbackUnit]
Enter the low reference value limit
for the motor shaft speed [RPM].
This is also the lowest feedback
value, see also
. Set
terminal 29 to digital input
(
parameter 5-02 Terminal 29 Mode
=
[0] input
(default) and
parameter 5-13 Terminal 29 Digital
Input
= applicable value).
5-53 Term. 29 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-999999.999
- 999999.999
Reference-
FeedbackUnit]
Enter the high reference value
[RPM] for the motor shaft speed
and the high feedback value, see
also
. Select terminal 29
as a digital input
(
parameter 5-02 Terminal 29 Mode
=
[0] input
(default) and
parameter 5-13 Terminal 29 Digital
Input
= applicable value).
5-54 Pulse Filter Time Constant #29
Range:
Function:
100
ms
*
[5 - 1000
ms]
Enter the pulse filter time constant. The
pulse filter dampens oscillations of the
feedback signal. If there is much noise in
the system, this is an advantage. A high
time constant value results in better
dampening but also increases the time
delay through the filter.
Parameter Descriptions