0-20 Display Line 1.1 Small
Option:
Function:
[2137]
Ext. 2 Reference
[Unit]
[2138]
Ext. 2 Feedback
[Unit]
[2139]
Ext. 2 Output [%]
[2157]
Ext. 3 Reference
[Unit]
[2158]
Ext. 3 Feedback
[Unit]
[2159]
Ext. 3 Output [%]
0-21 Display Line 1.2 Small
Select a variable for display in line 1, middle position. The
options are the same as those listed for
parameter 0-20 Display
Line 1.1 Small
.
0-22 Display Line 1.3 Small
Select a variable for display in line 1, right position. The options
are the same as those listed for
parameter 0-20 Display Line 1.1
Small
.
0-23 Display Line 2 Large
Select a variable for display in line 2. The options are the same
as those listed for
parameter 0-20 Display Line 1.1 Small
.
0-24 Display Line 3 Large
Select a variable for display in line 3. The options are the same
as those listed for
parameter 0-20 Display Line 1.1 Small
.
0-25 My Personal Menu
Range:
Function:
Size
related
*
[0 - 9999]
Define up to 50 parameters to
appear in the
Q1 Personal Menu
,
accessible via the [Quick Menu] key
on the LCP. The parameters are
shown in the
Q1 Personal Menu
in
the order they are programmed
into this array parameter. Delete
parameters by setting the value to
0000.
For example, this can be used to
provide quick, simple access to just
1 or up to 50 parameters, which
require changing on a regular basis
(for example, for plant maintenance
reasons) or by an OEM to enable
simple commissioning of their
equipment.
4.1.4 0-3* LCP Custom Readout
It is possible to customize the display elements for various
purposes:
•
Custom readout. Value proportional to speed
(linear, squared, or cubed depending on unit
selected in
parameter 0-30 Custom Readout Unit
).
•
Display text. Text string stored in a parameter.
Custom readout
The calculated value to be shown is based on the settings
in:
•
Parameter 0-30 Custom Readout Unit
.
•
Parameter 0-31 Custom Readout Min Value
(linear
only).
•
Parameter 0-32 Custom Readout Max Value
.
•
Parameter 4-13 Motor Speed High Limit [RPM]
.
•
Parameter 4-14 Motor Speed High Limit [Hz]
.
•
Actual speed.
Custom Readout (Value)
P 16-09
Custom Readout
Unit P 0-30
Max value
P 0-32
Min value
P 0-31
Linear
units only
Quadr
atic Unit (P
ressur
e)
Cubic Unit (P
ow
er)
Motor Speed
Motor Speed
High limit
P 4-13 (RPM)
P 4-14 (Hz)
0
130B
T105.12
Lin
ear
Un
it (e
.g. s
pe
ed
an
d fl
ow
)
Illustration 4.4 Custom Readout
The relation depends on the type of unit selected in
parameter 0-30 Custom Readout Unit
:
Unit type
Speed relation
Dimensionless
Linear
Speed
Flow, volume
Flow, mass
Velocity
Length
Temperature
Pressure
Quadratic
Power
Cubic
Table 4.2 Speed Relations for Different Unit Types
Parameter Descriptions
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
29
4
4