4.7.7 6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4–20 mA. Common
terminal (terminal X30/8) is the same terminal and
electrical potential for analog common connection.
Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
Option:
Function:
Select the function of terminal X30/8 as an
analog current output. Depending on the
selection, the output is either a 0–20 mA or
4–20 mA output. The current value can be
read out in the LCP in
parameter 16-65 Analog Output 42 [mA]
.
[0]
No
operation
When no signal on the analog output is
present.
[100] Output
frequency
[101] Reference
Parameter 3-00 Reference Range
[Min. - Max.]
0% = 0 mA; 100% = 20 mA.
Parameter 3-00 Reference Range
[-Max. - Max.]
-100% = 0 mA; 0% = 10 mA; +100% = 20
mA
[102] Feedback
[103] Motor
Current
The value is taken from
. The inverter maximum current
(160% current) is equal to 20 mA.
Example: Inverter normal current (11 kW) =
24 A. 160% = 38.4 A. Motor normal current
= 22 A, readout is 11.46 mA.
20 mA x 22 A
38 . 4 A
= 11 . 46 mA
In case the normal motor current is equal to
20 mA, the output setting of
parameter 6-62 Terminal X30/8 Max. Scale
is:
I
VLT
Max.
x 100
I
Motor
Norm
= 38 . 4 x 100
22
= 175 %
[104] Torque rel
to limit
The torque setting is related to the setting in
parameter 4-16 Torque Limit Motor Mode
[105] Torq relate
to rated
The torque is related to the motor torque
setting.
[106] Power
Taken from
parameter 1-20 Motor Power [kW]
.
[107] Speed
Taken from
. 20 mA = value in
parameter 3-03 Maximum Reference
.
[109] Max Out
Freq
In relation to
[130] Output freq.
4-20mA
0 Hz = 4 mA, 100 Hz = 20 mA.
[131] Reference
4-20mA
Parameter 3-00 Reference Range
[Min-Max]
0% = 4 mA; 100% = 20 mA
Parameter 3-00 Reference Range
[-Max-Max]
-100% = 4 mA; 0% = 12 mA; +100% =
20 mA.
[132] Feedback
4-20mA
6-60 Terminal X30/8 Output
Option:
Function:
[133] Motor cur.
4-20mA
The value is taken from
. The inverter maximum current
(160% current) is equal to 20 mA.
Example: Inverter normal current (11 kW) is
24 A. 160% = 38.4 A. Motor normal current
is 22 A, the readout is 11.46 mA.
16 mA x 22 A
38 . 4 A
+ 4 mA = 13 . 17 mA
In case the normal motor current is equal to
20 mA, the output setting of
parameter 6-52 Terminal 42 Output Max Scale
is:
I
VLT
Max
x 100
I
Motor
Norm
= 38 . 4 x 100
22
= 175 %
[134] Torq.% lim
4-20 mA
The torque setting is related to the setting in
parameter 4-16 Torque Limit Motor Mode
.
[135] Torq.% nom
4-20mA
The torque setting is related to the motor
torque setting.
[136] Power
4-20mA
Taken from
parameter 1-20 Motor Power [kW]
.
[137] Speed
4-20mA
Taken from
. 20 mA = value in
parameter 3-03 Maximum Reference
[139] Bus ctrl.
0-20 mA
An output value set from fieldbus process
data. The output works independently of
internal functions in the frequency converter.
[140] Bus ctrl.
4-20 mA
An output value set from fieldbus process
data. The output works independently of
internal functions in the frequency converter.
[150] Max Out Fr
4-20mA
0 Hz = 0 mA,
= 20 mA.
[255] DC Link
4-20mA
Enable the function of outputting the DC
link voltage on analog outputs. It scales the
output according to the maximum and
minimum voltage of the current drive size.
6-61 Terminal X30/8 Min. Scale
Range:
Function:
0 %
*
[0 - 200 %]
Scales the minimum output of the
selected analog signal on terminal
X30/8. Scale the minimum value as
a percentage of the maximum
signal value. For example, enter the
value 25% if the output should be
0 mA at 25% of the maximum
output value. The value can never
exceed the corresponding setting in
parameter 6-62 Terminal X30/8 Max.
Scale
if the value is below 100%.
This parameter is active when VLT
®
General Purpose I/O MCB 101 is
mounted in the frequency
converter.
Parameter Descriptions
VLT® AutomationDrive FC 361
86
Danfoss A/S © 03/2019 All rights reserved.
MG06J202