5-40 Function Relay
Option:
Function:
[7]
Run in
range/no warn
The motor runs within the
programmed current and the speed
ranges set in
parameter 4-50 Warning Current Low
and
. No warnings.
[8]
Run on ref/no
warn
The motor runs at reference speed.
No warnings.
[9]
Alarm
An alarm activates the output. No
warnings.
[10]
Alarm or
warning
An alarm or a warning activates the
output.
[11]
At torque limit The torque limit set in
parameter 4-16 Torque Limit Motor
Mode
or
has been exceeded.
[12]
Out of current
range
The motor current is outside the
range set in
.
[13]
Below current,
low
The motor current is lower than set
in
parameter 4-50 Warning Current
Low
.
[14]
Above current,
high
The motor current is higher than
set in
parameter 4-51 Warning
Current High
.
[15]
Out of speed
range
Output speed/frequency is outside
the frequency range set in
parameter 4-52 Warning Speed Low
and
[16]
Below speed,
low
Output speed is lower than the
setting in
parameter 4-52 Warning
Speed Low
.
[17]
Above speed,
high
Output speed is higher than the
setting in
[18]
Out of feedb.
range
Feedback is outside the range set
in
parameter 4-56 Warning Feedback
Low
and
parameter 4-57 Warning
Feedback High
.
[19]
Below
feedback, low
Feedback is below the limit set in
parameter 4-56 Warning Feedback
Low
.
[20]
Above
feedback, high
Feedback is above the limit set in
parameter 4-57 Warning Feedback
High
.
[21]
Thermal
warning
Thermal warning turns on when the
temperature exceeds the limit
either in motor, frequency
5-40 Function Relay
Option:
Function:
converter, brake resistor, or
connected thermistor.
[22]
Ready,no
thermal W
The frequency converter is ready for
operation and there is no overtem-
perature warning.
[23]
Remote,ready,
no TW
The frequency converter is ready for
operation and is in
auto-on
mode.
There is no overtemperature
warning.
[24]
Ready, Voltage
OK
The frequency converter is ready for
operation and the mains voltage is
within the specified voltage range
(see the
General Specifications
section in the
design guide
).
[25]
Reverse
The motor runs (or is ready to run)
clockwise when logic = 0 and
counterclockwise when logic = 1.
The output changes as soon as the
reversing signal is applied.
[26]
Bus OK
Active communication (no timeout)
via the serial communication port.
[27]
Torque limit &
stop
Use for performing a coasted stop
in a torque limit condition. If the
frequency converter has received a
stop signal and is in torque limit,
the signal is logic 0.
[31]
Relay 123
Digital output/relay is activated
when
[0] Control Word
is selected in
parameter group 8-** Comm. and
Options
.
[35]
External
Interlock
[36]
Control word
bit 11
Activate relay 1 by control word
from fieldbus. No other functional
impact in the frequency converter.
Typical application: Controlling
auxiliary device from fieldbus. The
function is valid when
[0] FC profile
in
parameter 8-10 Control Word
Profile
is selected.
[37]
Control word
bit 12
Activate relay 2 by control word
from fieldbus. No other functional
impact in the frequency converter.
Typical application: Controlling
auxiliary device from fieldbus. The
function is valid when
[0] FC profile
in
parameter 8-10 Control Word
Profile
is selected.
[38]
Motor
feedback error
Failure in the speed feedback loop
from motor running in closed loop.
The output can eventually be used
Parameter Descriptions
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
73
4
4