13-52 SL Controller Action
Option:
Function:
[29]
Start timer 0
Starts timer 0, see
parameter 13-20 SL Controller Timer
for further description.
[30]
Start timer 1
Starts timer 1, see
parameter 13-20 SL Controller Timer
for further description.
[31]
Start timer 2
Starts timer 2, see
parameter 13-20 SL Controller Timer
for further description.
[32]
Set digital out
A low
Any output with smart logic output
A is low.
[33]
Set digital out
B low
Any output with smart logic output
B is low.
[34]
Set digital out
C low
Any output with smart logic output
C is low.
[35]
Set digital out
D low
Any output with smart logic output
D is low.
[36]
Set digital out
E low
Any output with smart logic output
E is low.
[37]
Set digital out
F low
Any output with smart logic output
F is low.
[38]
Set digital out
A high
Any output with smart logic output
A is high.
[39]
Set digital out
B high
Any output with smart logic output
B is high.
[40]
Set digital out
C high
Any output with smart logic output
C is high.
[41]
Set digital out
D high
Any output with smart logic output
D is high.
[42]
Set digital out
E high
Any output with smart logic output
E is high.
[43]
Set digital out
F high
Any output with smart logic output
F is high.
[60]
Reset Counter
A
Resets counter A to 0.
[61]
Reset Counter
B
Resets counter B to 0.
[70]
Start timer 3
Starts timer 3, see
parameter 13-20 SL Controller Timer
for further description.
[71]
Start timer 4
Starts timer 4, see
parameter 13-20 SL Controller Timer
for further description.
[72]
Start timer 5
Starts timer 5, see
parameter 13-20 SL Controller Timer
for further description.
13-52 SL Controller Action
Option:
Function:
[73]
Start timer 6
Starts timer 6, see
parameter 13-20 SL Controller Timer
for further description.
[74]
Start timer 7
Starts timer 7, see
parameter 13-20 SL Controller Timer
for further description.
[80]
Sleep Mode
4.13 Parameters: 14-** Special Functions
14-00 Switching Pattern
Option:
Function:
Select the switching pattern: 60
°
AVM or SFAVM.
NOTICE
The frequency converter may
adjust the switching pattern
automatically to avoid a trip.
[0]
60 AVM
[1]
*
SFAVM
14-01 Switching Frequency
Select the frequency converter switching frequency. Changing
the switching frequency reduces acoustic noise from the motor.
Default values depend on power size.
Option:
Function:
NOTICE
The output frequency value of
the frequency converter must
never exceed 10% of the
switching frequency. When the
motor is running, adjust the
switching frequency in
parameter 14-01 Switching
Frequency
to minimize motor
noise.
NOTICE
To avoid a trip, the frequency
converter can adjust the
switching frequency automat-
ically.
[0]
1.0 kHz
[1]
1.5 kHz
[2]
2.0 kHz
[3]
2.5 kHz
[4]
3.0 kHz
[5]
3.5 kHz
[6]
4.0 kHz
[7]
5.0 kHz
Parameter Descriptions
Programming Guide