The standard terminals are 18, 19, 27, 29, 32, and 33. VLT
®
General Purpose I/O MCB 101 terminals are X30/2, X30/3,
and X30/4. Terminal 29 functions as an output.
Functions dedicated to only 1 digital input are stated in
the associated parameter.
All digital inputs can be programmed to these functions:
[0]
No
operation
No reaction to signals transmitted to the
terminal.
[1]
Reset
Resets frequency converter after a trip/alarm.
Not all alarms can be reset.
[2]
Coast
inverse
(Default digital input 27): Coast stop, inverted
input (NC). The frequency converter leaves the
motor in free mode. Logic 0
⇒
coast stop.
[3]
Coast and
reset
inverse
Reset and coast stop inverted input (NC).
Leaves motor in free mode and resets
frequency converter. Logic 0
⇒
coast stop and
reset.
[4]
Quick stop
inverse
Inverted input (NC). Generates a stop in
accordance with quick stop ramp time set in
parameter 3-81 Quick Stop Ramp Time
. When
the motor stops, the shaft is in free mode.
Logic 0
⇒
quick stop.
[5]
DC brake
inverse
Inverted input for DC brake (NC). Stops motor
by energizing it with a DC current for a certain
time period. See
to
parameter 2-03 DC Brake Cut In Speed
. The function is only active when the
value in
parameter 2-02 DC Braking Time
is
different from 0. Logic 0
⇒
DC brake.
[6]
Stop
inverse
Stop inverted function. Generates a stop
function when the selected terminal goes from
logical level 1 to logical level 0.
The stop is performed according to the
selected ramp time:
•
Parameter 3-42 Ramp 1 Ramp Down
Time
•
Parameter 3-52 Ramp 2 Ramp Down
Time
•
Parameter 3-62 Ramp 3 Ramp down
Time
, and
•
Parameter 3-72 Ramp 4 Ramp Down
Time
NOTICE
When the frequency converter is at the
torque limit and has received a stop
command, it may not stop by itself. To
ensure that the frequency converter
stops, configure a digital output to
[27]
Torque limit and stop
. Connect this
digital output to a digital input that is
configured as coast.
[8]
Start
(Default digital input 18): Select start for a
start/stop command. Logic 1 = start,
logic 0 = stop.
[9]
Latched
start
If a pulse is applied for minimum 2 ms, the
motor starts. The motor stops when stop
inverse is activated, or a reset command (via
DI) is given.
[10] Reversing
(Default digital input 19). Change the direction
of motor shaft rotation. Select logic 1 to
reverse. The reversing signal only changes the
direction of rotation. It does not activate the
start function. Select both directions in
parameter 4-10 Motor Speed Direction
. The
function is not active in process closed loop.
[11] Start
reversing
Used for start/stop and for reversing on the
same wire. Signals on start are not allowed at
the same time.
[12] Enable
start
forward
Disengages the counterclockwise movement
and allows clockwise direction.
[13] Enable
start
reverse
Disengages the clockwise movement and
allows counterclockwise direction.
[14] Jog
(Default digital input 29): Activate jog speed.
See
parameter 3-11 Jog Speed [Hz]
.
[15] Preset
reference
on
Shifts between external reference and preset
reference. It is assumed that
[1] External/preset
has been selected in
. Logic 0 = external reference active;
logic 1 = 1 of the 8 preset references is active.
[16] Preset ref
bit 0
Preset reference bit 0, 1, and 2 enable a choice
between 1 of the 8 preset references according
to
[17] Preset ref
bit 1
Same as
[16] Preset ref bit 0
.
[18] Preset ref
bit 2
Same as
[16] Preset ref bit 0
.
Preset ref. bit
2
1
0
Preset ref. 0
0
0
0
Preset ref. 1
0
0
1
Preset ref. 2
0
1
0
Preset ref. 3
0
1
1
Preset ref. 4
1
0
0
Preset ref. 5
1
0
1
Preset ref. 6
1
1
0
Preset ref. 7
1
1
1
Table 4.9 Preset Reference Bit
[19] Freeze
ref
Freezes the actual reference, which is now the
point of enable/condition to be used for
[21] Speed
up
and
[22] Speed down
. If speed up/speed down
is used, the speed change always follows ramp 2
(
parameter 3-51 Ramp 2 Ramp Up Time
and
parameter 3-52 Ramp 2 Ramp Down Time
) in the
range 0–
parameter 3-03 Maximum Reference
Parameter Descriptions
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
67
4
4