3-01 Reference/Feedback Unit
Option:
Function:
[172]
in WG
[173]
ft WG
[180]
HP
3-02 Minimum Reference
Range:
Function:
Size
related
*
[ -999999.999
- par. 3-03
Reference-
FeedbackUnit]
Enter the minimum reference. The
minimum reference is the lowest
value obtainable by summing all
references.
Minimum reference is active only
when
is set to
[0] Min.- Max.
The minimum reference unit
matches the unit selected in
parameter 3-01 Reference/Feedback
Unit
.
3-03 Maximum Reference
Range:
Function:
Size
related
*
[ par. 3-02 -
999999.999
Reference-
FeedbackUnit]
Enter the maximum reference. The
maximum reference is the highest
value obtainable by summing all
references.
The maximum reference unit
matches the unit selected in
parameter 3-00 Reference Range
.
3-04 Reference Function
Option:
Function:
[0]
Sum
Sums both external and preset
reference sources.
[1]
External/Preset Use either the preset or the
external reference source.
Shift between external and preset
via a command or a digital input.
4.4.2 3-1* References
Select the preset references. Select
Preset ref. bit 0/1/2 [16],
[17], or [18]
for the corresponding digital inputs in
parameter group 5-1* Digital Inputs
.
3-10 Preset Reference
Array [8]
Range: 0-7
Range:
Function:
0 %
*
[-100 -
100 %]
Enter up to 8 different preset
references (0–7) in this parameter,
using array programming. The
preset reference is stated as a
percentage of the value Ref
MAX
3-10 Preset Reference
Array [8]
Range: 0-7
Range:
Function:
(
). If a Ref
MIN
different from
0 (
) is programmed, the
preset reference is calculated as a
percentage of the full reference
range, that is on the basis of the
difference between Ref
MAX
and
Ref
MIN
. Afterwards, the value is
added to Ref
MIN
. When using preset
references, select preset reference
bit 0/1/2 [16], [17] or [18] for the
corresponding digital inputs in
parameter group 5-1* Digital Inputs
.
[P 5-13=Preset ref. bit 0]
Preset
[P 5-14=Preset ref. bit 1]
[P 5-15=Preset ref. bit 2]
10101010
76543210
29
12 (+24V)
11001100
32
11110000
33
130BA149.10
Illustration 4.14 Preset Reference
Preset ref. bit
2
1
0
Preset ref. 0
0
0
0
Preset ref. 1
0
0
1
Preset ref. 2
0
1
0
Preset ref. 3
0
1
1
Preset ref. 4
1
0
0
Preset ref. 5
1
0
1
Preset ref. 6
1
1
0
Preset ref. 7
1
1
1
Table 4.6 Preset Reference Bits
3-11 Jog Speed [Hz]
Range:
Function:
Size
related
*
[ 0 - par. 4-14
Hz]
The jog speed is a fixed output
speed at which the frequency
converter is running when the jog
function is activated.
See also
Parameter Descriptions
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
51
4
4
Summary of Contents for VLT AutomationDrive FC 361
Page 2: ......