5.2.7 6-** Analog In/Out
Param
eter
numb
er
Parameter description
Default value
4 set-up
Change
during
operation
Conversion
index
Type
6-0* Analog I/O Mode
6-00
Live Zero Timeout Time
10 s
All set-ups
TRUE
0
Uint8
6-01
Live Zero Timeout Function
[0] Off
All set-ups
TRUE
–
Uint8
6-1* Analog Input 1
6-10
Terminal 53 Low Voltage
ExpressionLimit
All set-ups
TRUE
-2
Int16
6-11
Terminal 53 High Voltage
10 V
All set-ups
TRUE
-2
Int16
6-12
Terminal 53 Low Current
0.14 mA
All set-ups
TRUE
-5
Int16
6-13
Terminal 53 High Current
20 mA
All set-ups
TRUE
-5
Int16
6-14
Terminal 53 Low Ref./Feedb. Value
0 N/A
All set-ups
TRUE
-3
Int32
6-15
Terminal 53 High Ref./Feedb. Value
ExpressionLimit
All set-ups
TRUE
-3
Int32
6-16
Terminal 53 Filter Time Constant
0.01 s
All set-ups
TRUE
-2
Uint16
6-2* Analog Input 2
6-20
Terminal 54 Low Voltage
ExpressionLimit
All set-ups
TRUE
-2
Int16
6-21
Terminal 54 High Voltage
10 V
All set-ups
TRUE
-2
Int16
6-22
Terminal 54 Low Current
ExpressionLimit
All set-ups
TRUE
-5
Int16
6-23
Terminal 54 High Current
20 mA
All set-ups
TRUE
-5
Int16
6-24
Terminal 54 Low Ref./Feedb. Value
0 N/A
All set-ups
TRUE
-3
Int32
6-25
Terminal 54 High Ref./Feedb. Value
ExpressionLimit
All set-ups
TRUE
-3
Int32
6-26
Terminal 54 Filter Time Constant
0.01 s
All set-ups
TRUE
-2
Uint16
6-3* Analog Input 3
6-30
Terminal X30/11 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-31
Terminal X30/11 High Voltage
10 V
All set-ups
TRUE
-2
Int16
6-34
Term. X30/11 Low Ref./Feedb. Value
0 N/A
All set-ups
TRUE
-3
Int32
6-35
Term. X30/11 High Ref./Feedb. Value
ExpressionLimit
All set-ups
TRUE
-3
Int32
6-36
Term. X30/11 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
6-4* Analog Input 4
6-40
Terminal X30/12 Low Voltage
0.07 V
All set-ups
TRUE
-2
Int16
6-41
Terminal X30/12 High Voltage
10 V
All set-ups
TRUE
-2
Int16
6-44
Term. X30/12 Low Ref./Feedb. Value
0 N/A
All set-ups
TRUE
-3
Int32
6-45
Term. X30/12 High Ref./Feedb. Value
ExpressionLimit
All set-ups
TRUE
-3
Int32
6-46
Term. X30/12 Filter Time Constant
0.001 s
All set-ups
TRUE
-3
Uint16
6-5* Analog Output 1
6-50
Terminal 42 Output
ExpressionLimit
All set-ups
TRUE
–
Uint8
6-51
Terminal 42 Output Min Scale
0 %
All set-ups
TRUE
-2
Int16
6-52
Terminal 42 Output Max Scale
100 %
All set-ups
TRUE
-2
Int16
6-53
Term 42 Output Bus Ctrl
0 %
All set-ups
TRUE
-2
N2
6-54
Terminal 42 Output Timeout Preset
0 %
1 set-up
TRUE
-2
Uint16
6-55
Analog Output Filter
[0] Off
1 set-up
TRUE
–
Uint8
6-6* Analog Output 2
6-60
Terminal X30/8 Output
ExpressionLimit
All set-ups
TRUE
–
Uint8
6-61
Terminal X30/8 Min. Scale
0 %
All set-ups
TRUE
-2
Int16
6-62
Terminal X30/8 Max. Scale
100 %
All set-ups
TRUE
-2
Int16
6-63
Terminal X30/8 Bus Control
0 %
All set-ups
TRUE
-2
N2
6-64
Terminal X30/8 Output Timeout Preset
0 %
1 set-up
TRUE
-2
Uint16
Parameter Lists
VLT® AutomationDrive FC 361
166
Danfoss A/S © 03/2019 All rights reserved.
MG06J202