0-10 Active Set-up
Option:
Function:
Select the set-up to control the
frequency converter functions.
[0]
Factory setup
Cannot be changed. It contains the
Danfoss data set and can be used
as a data source when returning
the other set-ups to a known state.
[1]
*
Set-up 1
[1] Set-up 1
to
[4] Set-up 4
are the 4
separate parameter set-ups within
which all parameters can be
programmed.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Multi Set-up
Remote set-up selections using
digital inputs and the serial
communication port. This set-up
uses the settings from
parameter 0-12 This Set-up Linked to
.
Stop the frequency converter
before making changes to open
and closed-loop functions.
Use
to copy a set-up to 1 or all
other set-ups. Stop the frequency converter before
switching between set-ups where parameters marked
not
changeable during operation
have different values. To avoid
conflicting settings of the same parameter within 2
different set-ups, link the set-ups together using
parameter 0-12 This Set-up Linked to
. Parameters which are
not changeable during operation
are marked FALSE in the
parameter lists in
0-11 Edit Set-up
Option:
Function:
Select the set-up to be edited (that
is programmed) during operation;
either the active set-up or 1 of the
inactive set-ups.
[0]
Factory setup
Cannot be edited but it is useful as
a data source to return the other
set-ups to a known state.
[1]
*
Set-up 1
[1] Set-up 1
to
[4] Set-up 4
can be
edited freely during operation,
independently of the active set-up.
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9]
Active Set-up
Can also be edited during
operation. Edit the selected set-up
from a range of sources: LCP, FC
RS485, FC USB, or up to 5 fieldbus
sites.
130BA199.10
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
P 0-11
P 0-11
P 0-11
P 0-11
Set-up
Set-up
Set-up
Set-up
PLC Fieldbus
Illustration 4.1 Edit Set-up