4.15.5 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
*
[ 0 - 1023 ]
View the signal states from the
active digital inputs. Example: Input
18 corresponds to bit number 5, 0
= no signal, 1 = connected signal.
Bit 6 works in the opposite way, on
= 0, off = 1 (Safe Torque Off input).
Bit 0
Digital input terminal
33.
Bit 1
Digital input terminal
32.
Bit 2
Digital input terminal
29.
Bit 3
Digital input terminal
27.
Bit 4
Digital input terminal
19.
Bit 5
Digital input terminal
18.
Bit 6
Digital input terminal
37.
Bit 7
Digital input VLT
®
General Purpose I/O
MCB 101 terminal X30/4.
Bit 8
Digital input VLT
®
General Purpose I/O
MCB 101 terminal X30/3.
Bit 9
Digital input VLT
®
General Purpose I/O
MCB 101 terminal X30/2.
Bit 10–
63
Reserved for future
terminals.
Table 4.20 Active Digital Inputs
D I T - 3 3
D I T - 3 2
D I T - 2 9
D I T - 2 7
D I T - 1 9
D I T - 1 8
D I T - 3 7
D I X 3 0/4
D I X 3 0/3
D I X 3 0/2
e30bg756.10
0 0
0 0 0 0 0 0 0 0 0 0 0 0 0 0
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Illustration 4.47 Relay Settings
16-61 Terminal 53 Switch Setting
Option:
Function:
View the setting of input terminal
53.
[0]
*
Current
[1]
Voltage
16-62 Analog Input 53
Range:
Function:
0
*
[-20 - 20]
View the actual value at input 53.
16-63 Terminal 54 Switch Setting
View the setting of input terminal 54.
Option:
Function:
[0]
*
Current
[1]
Voltage
16-64 Analog Input 54
Range:
Function:
0
*
[-20 - 20]
View the actual value at input 54.
16-65 Analog Output 42 [mA]
Range:
Function:
0
*
[0 - 30]
View the actual value at output 42
in mA. The value shown reflects the
selection in
parameter 6-50 Terminal
42 Output
.
16-66 Digital Output [bin]
Range:
Function:
0
*
[0 - 15]
View the binary value of all digital
outputs.
16-67 Pulse Input #29 [Hz]
Range:
Function:
0
*
[0 - 130000 ] View the actual frequency rate on
terminal 29.
16-68 Freq. Input #33 [Hz]
Range:
Function:
0
*
[0 - 130000]
View the actual value of the
frequency applied at terminal 33 as
an impulse input.
16-69 Pulse Output #27 [Hz]
Range:
Function:
0
*
[0 - 40000]
View the actual value of pulses
applied to terminal 27 in digital
output mode.
Parameter Descriptions
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
147
4
4