5-40 Function Relay
Option:
Function:
[85]
SL digital
output F
See
parameter 13-52 SL Controller
Action
. Output F is low on smart
logic action
[37]
. Output F is high
on smart logic action
[43]
.
[120]
Local ref
active
Output is high when
parameter 3-13 Reference Site
=
[2]
Local
or when
parameter 3-13 Reference Site
=
[0]
Linked to hand auto
at the same
time as the LCP is in
hand-on
mode.
Reference site
set in
parameter 3-1
3 Reference
Site
Local
referen
ce
active
[120]
Remote
referenc
e
active
[121]
Reference site:
Local
parameter 3-13
Reference Site
[2] Local
1
0
Reference site:
Remote
parameter 3-13
Reference Site
[1] Remote
0
1
Reference site:
Linked to
Hand/ Auto
Hand
1
0
Hand
⇒
off
1
0
Auto
⇒
off
0
0
Auto
0
1
Table 4.13 Local Reference Active
[121]
Remote ref
active
Output is high when
parameter 3-13 Reference Site
=
[1]
Remote
or
[0] Linked to hand/auto
while the LCP is in
auto-on
mode.
See
[122]
No alarm
Output is high when no alarm is
present.
[123]
Start
command
activ
Output is high when the start
command is high (that is via digital
input, bus connection, [Hand On],
or [Auto On]), and a stop has been
last command.
[124]
Running
reverse
Output is high when the frequency
converter is running counter-
clockwise (the logical product of
the status bits
running
AND
reverse
).
5-40 Function Relay
Option:
Function:
[125]
Drive in hand
mode
Output is high when the frequency
converter is in
hand-on
mode (as
indicated by the LED light above
[Hand On]).
[126]
Drive in auto
mode
Output is high when the frequency
converter is in
auto-on
mode (as
indicated by LED on above [Auto
On]).
[189]
External Fan
Control
The internal logics for the internal
fan control is transferred to this
output to make it possible to
control an external fan (relevant for
HP duct cooling).
[193]
Sleep Mode
[194]
Broken Belt
[221]
IGBT-cooling
Use this option for handling the
overcurrent trips. When the
frequency converter detects an
overcurrent condition, it shows
alarm 13, Overcurrent
and triggers a
reset. If the overcurrent condition
occurs the 3
rd
time in a row, the
frequency converter shows
alarm
13, Overcurrent
and initiates a 3-
minute delay before the next reset.
5-41 On Delay, Relay
Array [20]
Range:
Function:
0.01 s
*
[0.01 - 600 s] Enter the delay of the relay cut-in
time. Select 1 of 2 internal
mechanical relays in an array
function. See
parameter 5-40 Function Relay
for
details.
Selected
Event
Relay
output
Selected
Event
Relay
output
On Delay
P 5-41
On Delay
P 5-41
Off Delay
P 5-42
130BA171.10
Illustration 4.26 On Delay, Relay
Parameter Descriptions
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
75
4
4