8-08 Readout Filtering
Use this function if the speed feedback value readouts on the
fieldbus fluctuate. Select
[1] Motor Data LP-Filter
if the function is
required. A power cycle is required for changes to take effect.
Option:
Function:
[1]
Motor Data
LP-Filter
Filtered fieldbus readouts of the
following parameters:
•
•
•
•
•
Parameter 16-16 Torque
[Nm]
.
•
Parameter 16-17 Speed
[RPM]
.
•
Parameter 16-22 Torque
[%]
.
•
Parameter 16-25 Torque
[Nm] High
.
4.9.2 8-1* Ctrl. Word Settings
8-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
for the fieldbus installed in slot A are visible in the LCP display.
For guidelines in selection of
[0] FC profile
and
[1] PROFIdrive
profile
, refer to the
design guide
.
For more guidelines in the selection of
[1] PROFIdrive profile
, refer
to the
installation guide
for the installed fieldbus.
Option:
Function:
[0]
*
FC profile
[1]
PROFIdrive
profile
8-13 Configurable Status Word STW
This is an array parameter with 16 elements, 1 element for each
bit in range 0–15. Elements 5 and 11–15 are configurable. Each
of the bits can be configured to any of the following options.
Option:
Function:
[0]
No function
The input is always low.
[1]
*
Profile Default
Depending on the profile set
in
parameter 8-10 Control
Profile
.
[2]
Alarm 68 Only
The input goes high
whenever
alarm 68, Safe
Torque Off activated
is active
and goes low whenever
alarm 68, Safe Torque Off
activated
is not active.
[3]
Trip excl Alarm 68
[10]
T18 DI status
[11]
T19 DI status
[12]
T27 DI status
[13]
T29 DI status
[14]
T32 DI status
[15]
T33 DI status
[21]
Thermal warning
[40]
Out of ref range
[49]
Derate active
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic Rule 0
[71]
Logic Rule 1
[72]
Logic Rule 2
[73]
Logic Rule 3
[74]
Logic Rule 4
[75]
Logic Rule 5
[80]
SL digital out A
[81]
SL digital out B
[82]
SL digital out C
[83]
SL digital out D
[84]
SL digital out E
[85]
SL digital out F
[92]
IGBT-cooling
See
parameter group 5-3*
Digital Outputs
.
[193]
Sleep Mode
[194]
Broken Belt
Parameter Descriptions
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
95
4
4