16-01 Reference [Unit]
Range:
Function:
0 Referen-
ceFeedback
Unit
*
[-999999 -
999999
Reference-
FeedbackUnit]
View the present reference value
applied on impulse or analog basis
in the unit resulting from the
configuration selected in
parameter 1-00 Configuration Mode
(Hz, Nm, or RPM).
16-02 Reference [%]
Range:
Function:
0 %
*
[-200 -
200 %]
View the total reference. The total
reference is the sum of digital,
analog, preset, bus, and freeze
references, plus catch up and slow
down.
16-03 Status Word
Range:
Function:
0
*
[0 - 65535 ]
View the status word sent from the
frequency converter via the serial
communication port in hex code.
16-05 Main Actual Value [%]
Range:
Function:
0 %
*
[-100 -
100 %]
View the 2-byte word sent with the
status word to the fieldbus master
reporting the main actual value.
16-09 Custom Readout
Range:
Function:
0 Custom-
ReadoutUni
t
*
[0 -
999999.99
CustomRea-
doutUnit]
View the value of custom readout
from
parameter 0-30 Unit for User-
defined Readout
to
parameter 0-32 Custom Readout Max
Value
.
4.15.2 16-1* Motor Status
16-10 Power [kW]
Range:
Function:
0 kW
*
[0 - 10000
kW]
Shows motor power in kW. The
value shown is calculated based on
the actual motor voltage and motor
current. The value is filtered, and
therefore approximately 1.3 s may
pass from when an input value
changes to when the data readout
values change. The resolution of
readout value on fieldbus is in
10 W steps.
16-11 Power [hp]
Range:
Function:
0 hp
*
[0 - 10000
hp]
View the motor power in hp. The
value shown is calculated based on
the actual motor voltage and motor
current. The value is filtered, and
therefore approximately 1.3 ms may
pass from when an input value
changes to when the data readout
values change.
16-12 Motor Voltage
Range:
Function:
0 V
*
[0 - 6000 V]
View the motor voltage, a
calculated value used for
controlling the motor.
16-13 Frequency
Range:
Function:
0 Hz
*
[0 - 6500 Hz] View the motor frequency without
resonance damping.
16-14 Motor current
Range:
Function:
0 A
*
[0 - 10000 A] View the motor current measured
as an average value, I
RMS
. The value
is filtered, and thus approximately
1.3 s may pass from when an input
value changes to when the data
readout values change.
16-15 Frequency [%]
Range:
Function:
0 %
*
[-100 -
100 %]
View a 2-byte word reporting the
actual motor frequency (without
resonance damping) as a
percentage (scale 0000–4000 hex)
of
. Set
parameter 9-16 PCD
Read Configuration
index 1 to send
it with the status word instead of
the MAV.
16-16 Torque [Nm]
Range:
Function:
0 Nm
*
[-3000 - 3000
Nm]
View the torque value with sign,
applied to the motor shaft. Linearity
is not exact between 160% motor
current and torque in relation to
the rated torque. Some motors
supply more than 160% torque.
Therefore, the minimum value and
the maximum value depend on the
maximum motor current and the
motor used. The value is filtered,
Parameter Descriptions
VLT® AutomationDrive FC 361
144
Danfoss A/S © 03/2019 All rights reserved.
MG06J202
4
4