13-40 Logic Rule Boolean 1
Option:
Function:
[47]
Up key
[
▲
] is pressed. Only available on the
graphical LCP.
[48]
Down key
[
▼
] is pressed. Only available on the
graphical LCP.
[50]
Comparator 4
[51]
Comparator 5
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[75]
Start
command
given
[76]
Digital input
x30/2
[77]
Digital input
x30/3
[78]
Digital input
x30/4
[83]
Broken Belt
[102]
Relay 1
[103]
Relay 2
13-41 Logic Rule Operator 1
Array [6]
Option:
Function:
Select the 1
st
logical operator to
use on the boolean inputs from
parameter 13-40 Logic Rule Boolean
1
and
parameter 13-42 Logic Rule
Boolean 2
.
Parameter numbers in square
brackets stand for the boolean
inputs of parameters in
parameter
group 13-** Smart Logic Control
.
[0]
DISABLED
Ignores:
•
Parameter 13-42 Logic Rule
Boolean 2
.
•
Parameter 13-43 Logic Rule
Operator 2
.
•
Parameter 13-44 Logic Rule
Boolean 3
.
[1]
AND
Evaluates the expression [13-40]
AND [13-42].
[2]
OR
Evaluates the expression [13-40] OR
[13-42].
13-41 Logic Rule Operator 1
Array [6]
Option:
Function:
[3]
AND NOT
Evaluates the expression [13-40]
AND NOT [13-42].
[4]
OR NOT
Evaluates the expression [13-40] OR
NOT [13-42].
[5]
NOT AND
Evaluates the expression NOT
[13-40] AND [13-42].
[6]
NOT OR
Evaluates the expression NOT
[13-40] OR [13-42].
[7]
NOT AND NOT Evaluates the expression NOT
[13-40] AND NOT [13-42].
[8]
NOT OR NOT
Evaluates the expression NOT
[13-40] OR NOT [13-42].
13-42 Logic Rule Boolean 2
Option:
Function:
[0]
False
Select the 2
nd
boolean (true or
false) input for the selected logic
rule. See
parameter 13-01 Start Event
and
parameter 13-02 Stop Event
for
more information.
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current
range
[8]
Below I low
[9]
Above I high
[10]
Out of speed
range
[11]
Below speed
low
[12]
Above speed
high
[13]
Out of feedb.
range
[14]
Below feedb.
low
[15]
Above feedb.
high
[16]
Thermal
warning
[17]
Mains out of
range
[18]
Reversing
[19]
Warning
[20]
Alarm (trip)
Parameter Descriptions
VLT® AutomationDrive FC 361
122
Danfoss A/S © 03/2019 All rights reserved.
MG06J202
4