16-70 Pulse Output #29 [Hz]
Range:
Function:
0
*
[0 - 40000 ]
View the actual value of pulses at
terminal 29 in digital output mode.
16-71 Relay Output [bin]
Range:
Function:
0
*
[0 - 511 ]
View the settings of all relays.
R eadout choic e (P ar . 16-71):
R ela y output (bin):
Reserved
Reserved
P o w er car d r ela y 02
P o w er car d r ela y 01
Reserved
e30bg757.10
0 0 0
0 0 bin
Illustration 4.48 Relay Settings
16-72 Counter A
Range:
Function:
0
*
[-2147483648
- 2147483647]
View the present value of counter
A. Counters are useful as
comparator operands, see
parameter 13-10 Comparator
Operand
.
Reset or change the value either via
digital inputs (
parameter group 5-1*
Digital Inputs
) or by using an SLC
action (
parameter 13-52 SL Controller
Action
).
16-73 Counter B
Range:
Function:
0
*
[-2147483648
- 2147483647]
View the present value of counter
B. Counters are useful as
comparator operands
(
parameter 13-10 Comparator
Operand
).
Reset or change the value either via
digital inputs (
parameter group 5-1*
Digital Inputs
) or by using an SLC
action (
parameter 13-52 SL Controller
Action
).
16-75 Analog In X30/11
Range:
Function:
0
*
[-20 - 20 ]
View the actual value at input
X30/11 of VLT
®
General Purpose I/O
MCB 101.
16-76 Analog In X30/12
Range:
Function:
0
*
[-20 - 20 ]
View the actual value at input
X30/12 of VLT
®
General Purpose I/O
MCB 101.
16-77 Analog Out X30/8 [mA]
Range:
Function:
0
*
[0 - 30 ]
View the actual value at input
X30/8 in mA.
4.15.6 16-8* Fieldbus & FC Port
Parameters for reporting the bus references and control
words.
16-80 Fieldbus CTW 1
Range:
Function:
0
*
[0 - 65535 ]
View the 2-byte control word (CTW)
received from the fieldbus master.
Interpretation of the control word
depends on the fieldbus option
installed and the control word
profile selected in
parameter 8-10 Control Profile
.
For more information, refer to the
relevant fieldbus manual.
16-82 Fieldbus REF 1
Range:
Function:
0
*
[-200 - 200 ]
View the 2-byte word sent with the
control word from the fieldbus
master to set the reference value.
For more information, refer to the
relevant fieldbus manual.
16-84 Comm. Option STW
Range:
Function:
0
*
[0 - 65535 ]
Show the status word of the
extended fieldbus communication
option.
For more information, refer to the
relevant fieldbus manual.
16-85 FC Port CTW 1
Range:
Function:
0
*
[0 - 65535 ]
View the 2-byte control word (CTW)
received from the fieldbus master.
Interpretation of the control word
depends on the fieldbus option
installed and the control word
profile selected in
parameter 8-10 Control Profile
.
Parameter Descriptions
VLT® AutomationDrive FC 361
148
Danfoss A/S © 03/2019 All rights reserved.
MG06J202
4
4