[20] Freeze
output
Freezes the actual motor frequency (Hz), which is
now the point of enable/condition to be used for
[21] Speed up
and
[22] Speed down
. If speed up/
speed down is used, the speed change always
follows ramp 2 (
and
parameter 3-52 Ramp 2 Ramp Down Time
)
in the range 0–
parameter 1-23 Motor Frequency
.
NOTICE
When freeze output is active, the frequency
converter cannot be stopped via a low
[8]
Start
signal. Stop the frequency converter
via a terminal programmed for
[2] Coasting
inverse
or
[3] Coast and reset inverse
.
[21] Speed
up
Select
[21] Speed up
and
[22] Speed down
for digital
control of the up/down speed (motor potenti-
ometer). Activate this function by selecting either
[19] Freeze ref
or
[20] Freeze output
. When speed
up/speed down is activated for less than 400 ms,
the resulting reference is increased/decreased by
0.1%. If speed up/speed down is activated for
more than 400 ms, the resulting reference follows
the setting in ramping up/down parameters 3-
x1/3-x2.
Shut down
Catch up
Unchanged speed
0
0
Reduced by %-value
1
0
Increased by %-value
0
1
Reduced by %-value
1
1
Table 4.10 Shut Down/Catch Up
[22] Speed
down
Same as
[21] Speed up
.
[23] Set-up
select bit 0
Select
[23] Set-up select bit 0
or select
[24] Set-
up select bit 1
to select 1 of the 4 set-ups. Set
to Multi Set-up.
[24] Set-up
select bit 1
(Default digital input 32): Same as
[23] Set-up
select bit 0
.
[28] Catch up
Increases reference value by percentage
(relative) set in
[29] Slow down Reduces reference value by percentage
(relative) set in
[34] Ramp bit 0 Enables a selection between 1 of the 4 ramps
available, according to
.
[35] Ramp bit 1 Same as
[34] Ramp bit 0
.
Preset ramp bit
1
0
Ramp 1
0
0
Ramp 2
0
1
Ramp 3
1
0
Ramp 4
1
1
Table 4.11 Preset Ramp Bit
[51] External
interlock
This function makes it possible to give an
external fault to the frequency converter. This
fault is treated in the same way as an
internally generated alarm.
[55] DigiPot
Increase
Increase signal to the digital potentiometer
function described in
parameter group 3-9*
Digital Pot. Meter
.
[56] DigiPot
Decrease
Decrease signal to the digital potentiometer
function described in
parameter group 3-9*
Digital Pot. Meter
.
[57] DigiPot
Clear
Clears the digital potentiometer reference
described in
parameter group 3-9* Digital Pot.
Meter
.
[62] Reset
Counter A
Input for reset of counter A.
[65] Reset
Counter B
Input for reset of counter B.
[66] Sleep Mode
[72] PID error
inverse
When enabled, this option inverts the
resulting error from the process PID controller.
Available only if
parameter 1-00 Configuration
Mode
is set to
[7] Extended PID Speed OL
.
[73] PID reset I-
part
When enabled, this option resets the I-part of
the process PID controller. Equivalent to
parameter 7-40 Process PID I-part Reset
.
Available only if
parameter 1-00 Configuration
Mode
is set to
[7] Extended PID Speed OL
.
[74] PID enable
Enables the extended process PID controller.
Equivalent to
. Available only if
parameter 1-00 Configuration Mode
is set to
[7]
Extended PID Speed OL
.
5-10 Terminal 18 Digital Input
Option:
Function:
[8]
*
Start Functions are described in
parameter group 5-1*
Digital Inputs
.
5-11 Terminal 19 Digital Input
Option:
Function:
[10]
*
Reversing Functions are described in
parameter group
5-1* Digital Inputs
.
5–12 Terminal 27 Digital Input
Option:
Function:
[2]
*
Coast inverse Functions are described in
parameter group
5-1* Digital Inputs
.
5-13 Terminal 29 Digital Input
Option:
Function:
Select the function from the available digital input
range and the additional options
[60] Counter A
,
[61]
Counter A
,
[63] Counter B
, and
[64] Counter B
.
Counters are used in smart logic control functions.
[14]
*
Jog Functions are described in
parameter group 5-1*
Digital Inputs
.
Parameter Descriptions
VLT® AutomationDrive FC 361
68
Danfoss A/S © 03/2019 All rights reserved.
MG06J202
4
4