2-17 Over-voltage Control
Option:
Function:
Overvoltage control (OVC) reduces
the risk of the frequency converter
tripping due to an overvoltage on
the DC-link caused by generative
power from the load.
[0]
*
Disabled
No OVC required.
[1]
Enabled (not
at stop)
Activates OVC except when using a
stop signal to stop the frequency
converter.
[2]
Enabled
Activates OVC.
NOTICE
Do not enable OVC in hoisting applications.
2-19 Over-voltage Gain
Range:
Function:
100 %
*
[10 - 200 %]
Select overvoltage gain.
4.4 Parameters: 3-** Reference/Ramps
Parameters for handling of reference, definition of
limitations, and configuration of the reaction of the
frequency converter to changes.
4.4.1 3-0* Reference Limits
3-00 Reference Range
Option:
Function:
Select the range of the reference
signal and the feedback signal.
Signal values can be positive only,
or positive and negative. The
minimum limit may have a negative
value, unless
[1] Speed closed loop
control or
[3] Process
is selected in
parameter 1-00 Configuration Mode
.
[0]
Min - Max
Select the range of the reference
signal and the feedback signal.
Signal values can be positive only,
or positive and negative. The
minimum limit may have a negative
value, unless
[1] Speed closed loop
control or
[3] Process
is selected in
parameter 1-00 Configuration Mode
.
[1]
-Max - +Max
For both positive and negative
values (both directions, relative to
parameter 4-10 Motor Speed
Direction
).
3-01 Reference/Feedback Unit
Option:
Function:
Select the unit to be used in
process PID control references and
feedbacks.
Parameter 1-00 Configu-
ration Mode
must be either
[3]
Process
.
[0]
None
[1]
%
[2]
RPM
[3]
Hz
[4]
Nm
[5]
PPM
[10]
1/min
[12]
Pulse/s
[20]
l/s
[21]
l/min
[22]
l/h
[23]
m³/s
[24]
m³/min
[25]
m³/h
[30]
kg/s
[31]
kg/min
[32]
kg/h
[33]
t/min
[34]
t/h
[40]
m/s
[41]
m/min
[45]
m
[60]
°C
[70]
mbar
[71]
bar
[72]
Pa
[73]
kPa
[74]
m WG
[80]
kW
[120]
GPM
[121]
gal/s
[122]
gal/min
[123]
gal/h
[124]
CFM
[125]
ft³/s
[126]
ft³/min
[127]
ft³/h
[130]
lb/s
[131]
lb/min
[132]
lb/h
[140]
ft/s
[141]
ft/min
[145]
ft
[150]
lb ft
[160]
°F
[170]
psi
[171]
lb/in²
Parameter Descriptions
VLT® AutomationDrive FC 361
50
Danfoss A/S © 03/2019 All rights reserved.
MG06J202
4
4
Summary of Contents for VLT AutomationDrive FC 361
Page 2: ......