4.13.2 14-2* Trip Reset
Parameters for configuring auto reset handling, special trip
handling, and control card self-test or initialization.
14-20 Reset Mode
Option:
Function:
Select the reset function after
tripping. Once reset, the frequency
converter can be restarted.
NOTICE
The motor may start without
warning. If the specified
number of automatic resets is
reached within 10 minutes, the
frequency converter enters
[0]
Manual reset
mode. After the
manual reset is performed, the
setting of
parameter 14-20 Reset Mode
returns to the original
selection. If the number of
automatic resets are not
reached within 10 minutes, or
when a manual reset is
performed, the internal
automatic reset counter
returns to 0.
NOTICE
Automatic reset is also valid
for resetting the Safe Torque
Off function in firmware
version 4.3x or earlier.
[0]
*
Manual reset
Select
[0] Manual reset
to perform a
reset via [Reset] or via the digital
inputs.
[1]
Automatic
reset x 1
Select
[1]-[12] Automatic reset x 1…
x20
to perform 1–20 automatic
resets after tripping.
[2]
Automatic
reset x 2
[3]
Automatic
reset x 3
[4]
Automatic
reset x 4
[5]
Automatic
reset x 5
[6]
Automatic
reset x 6
[7]
Automatic
reset x 7
[8]
Automatic
reset x 8
14-20 Reset Mode
Option:
Function:
[9]
Automatic
reset x 9
[10]
Automatic
reset x 10
[11]
Automatic
reset x 15
[12]
Automatic
reset x 20
[13]
Infinite auto
reset
Select this option for continuous
resetting after tripping.
[14]
Reset at
power-up
14-21 Automatic Restart Time
Range:
Function:
Size
related
*
[0 - 3600 s]
Enter the time interval from trip to
start of the automatic reset
function. This parameter is active
when
parameter 14-20 Reset Mode
is
set to
[1]–[13] Automatic reset
.
14-22 Operation Mode
Option:
Function:
Use this parameter to specify
normal operation; to perform tests;
or to initialize all parameters except
, and
. This
function is active only when the
power is cycled to the frequency
converter.
Select
[0] Normal operation
for
normal operation of the frequency
converter with the motor in the
selected application.
Select
[1] Control card test
to test
the analog and digital inputs and
outputs and the +10 V control
voltage. The test requires a test
connector with internal
connections. Use the following
procedure for the control card test:
1.
Select
[1] Control card test
.
2.
Disconnect the mains
supply and wait for the
indicator light in the
display to go out.
3.
Set switches S201 (A53)
and S202 (A54) to ON/I.
4.
Insert the test plug (see
).
Parameter Descriptions
VLT® AutomationDrive FC 361
132
Danfoss A/S © 03/2019 All rights reserved.
MG06J202
4
4