4.14 Parameters: 15-** Drive Information
4.14.1 15-0* Operating Data
15-00 Operating hours
Range:
Function:
0 h
*
[0 -
2147483647 h]
View how many hours the
frequency converter has run. The
value is saved when the frequency
converter is turned off.
15-01 Running Hours
Range:
Function:
0 h
*
[0 -
2147483647 h]
View how many hours the motor
has run. Reset the counter in
parameter 15-07 Reset Running
Hours Counter
. The value is saved
when the frequency converter is
turned off.
15-02 kWh Counter
Range:
Function:
0 kWh
*
[0 -
2147483647
kWh]
Register the power consumption of
the motor as an average value over
1 hour. Reset the counter in
parameter 15-06 Reset kWh Counter
.
15-03 Power Up's
Range:
Function:
0
*
[0 -
2147483647 ]
View the number of times the
frequency converter has been
powered up.
15-04 Over Temp's
Range:
Function:
0
*
[0 - 65535 ]
View the number of frequency
converter temperature faults.
15-05 Over Volt's
Range:
Function:
0
*
[0 - 65535 ]
View the number of frequency
converter overvoltages.
15-06 Reset kWh Counter
Option:
Function:
[0]
*
Do not reset
No reset of the kWh counter is
required.
[1]
Reset counter
Press [OK] to reset the kWh counter
to 0 (see
15-07 Reset Running Hours Counter
Option:
Function:
[0]
*
Do not reset
15-07 Reset Running Hours Counter
Option:
Function:
[1]
Reset counter
To reset the running hours counter
to 0, select
[1] Reset
and press [OK]
(see
). This parameter cannot be
selected via the serial port, RS485.
Select
[0] Do not reset
if no reset of
the running-hours counter is
required.
4.14.2 15-1* Data Log Settings
The data log enables continuous logging of up to 4 data
sources (
parameter 15-10 Logging Source
) at individual rates
parameter 15-11 Logging Interval
). A trigger event
(
parameter 15-12 Trigger Event
) and window
(
parameter 15-14 Samples Before Trigger
) are used to start
and stop the logging conditionally.
15-10 Logging Source
Option:
Function:
Select which variables are to be
logged.
[0]
*
None
[1600]
Control Word
[1601]
Reference
[Unit]
[1602]
Reference %
[1603]
Status Word
[1610]
Power [kW]
[1611]
Power [hp]
[1612]
Motor Voltage
[1613]
Frequency
[1614]
Motor current
[1616]
Torque [Nm]
[1617]
Speed [RPM]
[1618]
Motor Thermal
[1620]
Motor Angle
[1621]
Torque [%]
High Res.
[1622]
Torque [%]
[1624]
Calibrated
Stator
Resistance
[1630]
DC Link
Voltage
[1634]
Heatsink
Temp.
[1635]
Inverter
Thermal
[1645]
Motor Phase U
Current
[1646]
Motor Phase V
Current
Parameter Descriptions
Programming Guide
MG06J202
Danfoss A/S © 03/2019 All rights reserved.
139