6-11 Terminal 53 High Voltage
Range:
Function:
10 V
*
[ par. 6-10 -
10 V]
Enter the high voltage value. This
analog input scaling value should
correspond to the high reference
feedback value set in
parameter 6-15 Terminal 53 High
Ref./Feedb. Value
.
6-12 Terminal 53 Low Current
Range:
Function:
0.14 mA
*
[ 0 - par. 6-13
mA]
Enter the low current value. This
reference signal should correspond
to the minimum reference value,
set in
. Set the value to exceed 2
mA in order to activate the live
zero timeout function in
parameter 6-01 Live Zero Timeout
Function
.
6-13 Terminal 53 High Current
Range:
Function:
20 mA
*
[ par. 6-12 -
20 mA]
Enter the high current value
corresponding to the high
reference/feedback set in
parameter 6-15 Terminal 53 High
Ref./Feedb. Value
.
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
Function:
0 Referen-
ceFeedback
Unit
*
[-999999.999
- 999999.999
Reference-
FeedbackUnit]
Enter the analog input scaling value
that corresponds to the low
voltage/low current set in
parameter 6-10 Terminal 53 Low
Voltage
and
parameter 6-12 Terminal
53 Low Current
.
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Function:
Size
related
*
[-999999.999
- 999999.999
Reference-
FeedbackUnit]
Enter the analog input scaling value
that corresponds to the maximum
reference feedback value set in
parameter 6-11 Terminal 53 High
Voltage
and
.
6-16 Terminal 53 Filter Time Constant
Range:
Function:
0.01 s
*
[0.01 - 10 s]
NOTICE
This parameter cannot be
adjusted while the motor is
running.
6-16 Terminal 53 Filter Time Constant
Range:
Function:
Enter the filter time constant. This
constant is a first-order digital low-
pass filter time for suppressing
electrical noise in terminal 53. A
high value improves dampening
but also increases the delay
through the filter.
4.7.3 6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog
input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
Function:
0.07 V
*
[ 0 - par. 6-21
V]
Enter the low voltage value. This
analog input scaling value should
correspond to the minimum
reference value set in
parameter 3-02 Minimum Reference
See also
6-21 Terminal 54 High Voltage
Range:
Function:
10 V
*
[ par. 6-20 -
10 V]
Enter the high voltage value. This
analog input scaling value should
correspond to the high reference
feedback value set in
parameter 6-25 Terminal 54 High
Ref./Feedb. Value
.
6-22 Terminal 54 Low Current
Range:
Function:
Size
related
*
[ 0 - par. 6-23
mA]
Enter the low current value. This
reference signal should correspond
to the minimum reference value,
set in
. Enter the value that
exceeds 2 mA to activate the live
zero timeout function in
parameter 6-01 Live Zero Timeout
Function
.
6-23 Terminal 54 High Current
Range:
Function:
20 mA
*
[ par. 6-22 -
20 mA]
Enter the high current value
corresponding to the high reference
feedback value set in
parameter 6-25 Terminal 54 High
Ref./Feedb. Value
.
Parameter Descriptions