0-51 Set-up Copy
Option:
Function:
[0]
*
No copy
No function.
[1]
Copy to set-up
1
Copies all parameters in the present
programming set-up (defined in
parameter 0-11 Programming Set-up
)
to set-up 1.
[2]
Copy to set-up
2
Copies all parameters in the present
programming set-up (defined in
parameter 0-11 Programming Set-up
)
to set-up 2.
[3]
Copy to set-up
3
Copies all parameters in the present
programming set-up (defined in
parameter 0-11 Programming Set-up
)
to set-up 3.
[4]
Copy to set-up
4
Copies all parameters in the present
programming set-up (defined in
parameter 0-11 Programming Set-up
)
to set-up 4.
[9]
Copy to all
Copies the parameters in the
present set-up to each of the set-
ups 1 to 4.
4.1.7 0-6* Password
0-60 Main Menu Password
Range:
Function:
100
*
[0 - 999 ]
Define the password for access to
the Main Menu via the [Main Menu]
key. If
is set to
[0] Full
access
, this parameter is ignored.
0-61 Access to Main Menu w/o Password
Option:
Function:
[0]
*
Full access
Disables password defined in
parameter 0-60 Main Menu
Password
.
[1]
Read only
Prevent unauthorized editing of
Main Menu
parameters.
[2]
No access
Prevent unauthorized viewing and
editing of
Main Menu
parameters.
If
[0] Full access
is selected,
parameter 0-60 Main Menu
Password
,
parameter 0-65 Personal Menu Password
, and
parameter 0-66 Access to Personal Menu w/o Password
are
ignored.
4.2 Parameters: 1-** Load and Motor
4.2.1 1-0* General Settings
Define whether the frequency converter operates in speed
mode or torque mode, and whether the internal PID
control should be active or not.
1-00 Configuration Mode
Option:
Function:
Select the application control
principle to be used when a remote
reference (that is via analog input
or fieldbus) is active. A remote
reference can only be active when
parameter 3-13 Reference Site
is set
to
[0] Linked to Hand/Auto
or
[1]
Remote
.
[0]
Speed open
loop
Enables speed control (without
feedback signal from motor) with
automatic slip compensation for
almost constant speed at varying
loads.
Compensations are active, but can
be disabled in
parameter group 1-0*
General Settings
. Set the speed
control parameters in
parameter
group 7-0* Speed PID Ctrl
.
[1]
Speed closed
loop
Enables speed closed-loop control
with feedback. Obtain full holding
torque at 0 RPM.
For increased speed accuracy,
provide a feedback signal and set
the speed PID control. Set the
speed control parameters in
parameter group 7-0* Speed PID Ctrl
.
[3]
Process
Enables the use of process control
in the frequency converter. Set the
process control parameters in
parameter groups 7-2* Process Ctrl.
Feedb.
and
7-3* Process PID Ctrl
.
[4]
Torque open
loop
Enables the use of torque open
loop in VVC
+
mode
(
parameter 1-01 Motor Control
Principle
). Set the torque PID
parameters in
parameter group 7-1*
Torque PI Control
.
[7]
Extended PID
Speed OL
Specific parameters in
parameter
groups 7-2* Process Ctrl. Feedb.
to
7-5* Ext. Process PID Ctrl
.
Parameter Descriptions
VLT® AutomationDrive FC 361
32
Danfoss A/S © 03/2019 All rights reserved.