0-12 This Set-up Linked to
Option:
Function:
To enable conflict-free changes
from 1 set-up to another during
operation, link set-ups containing
parameters which are
not
changeable during operation
. The
link ensures synchronizing of the
not changeable during operation
-
parameter values when moving
from 1 set-up to another during
operation.
Not changeable during
operation
-parameters can be
identified by the label FALSE in the
parameter lists in
Parameter 0-12 This Set-up Linked to
is used by
[9] Multi set-up
in
. Multi
set-up is used to move from 1 set-
up to another during operation
(that is while the motor is running).
Example:
Use multi set-up to shift from set-
up 1 to set-up 2 while the motor is
running. Program in set-up 1 first,
then ensure that set-up 1 and set-
up 2 are synchronized (or linked).
Synchronization can be performed
in 2 ways:
1. Select the following options:
•
[2] Set-up 2
in
•
[1] Set-up 1
in
parameter 0-12 This Set-up
Linked to
.
This starts the linking (synchro-
nizing) process.
130BP075.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[1]
Setup 1
Illustration 4.2 Set-up 1
OR
2. While still in set-up 1, copy set-
up 1 to set-up 2. Then set
parameter 0-12 This Set-up Linked to
to
[2] Set-up 2
. This starts the
linking process.
0-12 This Set-up Linked to
Option:
Function:
130BP076.10
0-12 This Set-up Linked to
0 RPM
0.00A
1(1)
Set-up Handling
0-1*
[2]
Setup 2
Illustration 4.3 Set-up 2
When completed,
parameter 0-13 Readout: Linked Set-
ups
reads {1,2} to indicate that all
not changeable during operation
-
parameters are now the same in
set-up 1 and set-up 2. If there are
changes to a
not changeable during
operation
parameter, for example
parameter 1-30 Stator Resistance (Rs)
,
in set-up 2, they are also changed
automatically in set-up 1. A switch
between set-up 1 and set-up 2
during operation is now possible.
[0]
*
Not linked
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
0-13 Readout: Linked Set-ups
Array [5]
Range:
Function:
0
*
[0 - 255 ]
View a list of all the set-ups linked
by
parameter 0-12 This Set-up Linked
to
. The parameter has 1 index for
each parameter set-up. The value
for each index shows which set-ups
are linked to that parameter set-up.
Index
LCP value
0
{0}
1
{1,2}
2
{1,2}
3
{3}
4
{4}
Table 4.1 Set-up Link Example
Parameter Descriptions
VLT® AutomationDrive FC 361
26
Danfoss A/S © 03/2019 All rights reserved.
MG06J202
4