Parameters
Parameter set 0
78
Controller BUS 6 T
5.94017.06
Baumüller Nürnberg GmbH
polarity of set torque value
Clockwise rotation of the motor shaft (seen from the front) takes place if the set torque value
and the polarity are positive.
Bit no.
Meaning
0
set torque value
0: positive polarity
1: negative polarity
1
reserved
2
actual torque value
0: positive polarity
1: negative polarity
3
analog actual torque value
0: unipolar pos. and neg. actual torque value [0 ... +10V]
1: bipolar
pos. actual torque value (bit no. 2 = 0)
[0 ... +10V]
neg. actual torque value (bit no. 2 = 1)
[0 ... -10V]
on PCB 3.9211 between X3:5 und X3:6
4 ... 15
reserved
positive torque limit value
negative torque limit value
bipolar torque limit value
Display of torque limitation. With M control a value < 1 % should be set.
The torque limit values limit torque either in positive or negative direction or symmetrically.
With analog set value input (I/O option board 3.9211)
a) X2:7 = +10 V or -10 V
X2:8 = 0 V
ID no. 32926 = 0
ID no. 82 = 100 %
ID no. 83 = -100 %
ID no. 92 = 100 %
b) X2:7 = +10 V
X2:8 = 0 V
ID no. 32926 = 1
ID no. 82 = 100 %
ID no. 83 = 0 %
ID no. 92 = 100 %
c)
X2:7 = -10 V
X2:8 = 0 V
ID no. 32926 = 1
ID no. 82 = 0 %
ID no. 83 = -100 %
ID no. 92 = 100 %
On exceeding the torque limit value the drive sets the message in Class 3 Diagnostics.
actual torque value
This parameter displays the current actual torque value.
Summary of Contents for BUS 6-T Series
Page 6: ...Abbreviations IV Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 10: ...Technical data 4 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 18: ...Assembly 12 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 22: ...Installation 16 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 40: ...Commissioning 34 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 52: ...Commissioning Torque control 46 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...