Parameter set 0
Parameters
Controller BUS 6 T
83
Baumüller Nürnberg GmbH
5.94017.06
torque threshold M
dx
If the actual torque value exceeds torque threshold M
dx
, the drive sets the message
M
d
³ M
dx
(ID no. 333) in Class 3 Diagnostics.
Display via LED H 401 red and via relay contacts X3:13 and X3:14 on printed circuit board
3.9211.
response time Pzkx (M
dx
)
The response time specifies for how long the torque threshold must be exceeded before a
message is displayed.
voltage failure time
After a voltage failure that lasts not longer than the set voltage failure time, the drive starts
independently if the power supply of the controller isn´t disturbed and the pulse enable and
controller enable is given. After a voltage failure that lasts longer the drive sets a message
in Class 1 Diagnostics.