Basic settings
Parameters
Controller BUS 6 T
55
Baumüller Nürnberg GmbH
5.94017.06
control type
Via this parameter the service personnel can specify the control type.
The torque limitation must be set to 0 % before switching to M control (0 V at X2:7 and
X2:8).
Value
Meaning
0
speed control
1
torque control
2
position control
3
reference run
4
spindle positioning
The functions position control, reference run and spindle positioning are not yet
implemented with synchronous motors.
analog mode
This parameter displays the analog mode.
Value
Meaning
0
main spindle drive
1
C axis mode
2
main spindle mode with set correction value
3
C axis mode with set correction value
4
analog torque control
set additive value
A set correction value can only be entered in analog mode.
Input: X3:1 and X3:2 from -10V .. +10V.
Value
Meaning
0
on
1
off
encoder type
The encoder used is set via this parameter.
Value
Meaning
0
incremental encoder
1
incremental encoder (sine)
2
resolver
Summary of Contents for BUS 6-T Series
Page 6: ...Abbreviations IV Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 10: ...Technical data 4 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 18: ...Assembly 12 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 22: ...Installation 16 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 40: ...Commissioning 34 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 52: ...Commissioning Torque control 46 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...