Parameters
Display and measuring parameters
68
Controller BUS 6 T
5.94017.06
Baumüller Nürnberg GmbH
amplifier warning temperature
If the amplifier temperature exceeds the amplifier warning temperature, the drive sets the
bit "amplifier warning temperature" in Class 2 Diagnostics (see ID no. 12).
NOTE
Exceeding the temperature does not cause pulse or controller inhibit.
amplifier shutdown temperature
If the amplifier temperature exceeds the amplifier shutdown temperature, the drive sets the
bit "amplifier shutdown temperature" in Class 1 Diagnostics (see ID no. 11).
NOTE
Exceeding the temperature causes controller inhibit.
motor warning temperature
If the motor temperature exceeds the motor warning temperature, the drive sets the bit
"excess motor temperature warning" in Class 2 Diagnostics (see ID no. 12). With DS motors
this function is not evaluated.
NOTE
Exceeding the temperature does not cause pulse or controller inhibit.
motor shutdown temperature
If the motor temperature exceeds the motor shutdown temperature, the drive sets the bit
"excess motor temperature shutdown" in Class 1 Diagnostics (see ID no. 11).
NOTE
Exceeding the temperature causes controller inhibit.
Summary of Contents for BUS 6-T Series
Page 6: ...Abbreviations IV Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 10: ...Technical data 4 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 18: ...Assembly 12 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 22: ...Installation 16 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 40: ...Commissioning 34 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 52: ...Commissioning Torque control 46 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...