Parameters
Parameter set 2
86
Controller BUS 6 T
5.94017.06
Baumüller Nürnberg GmbH
7.6 Parameter set 2
7.6.1 Velocity and ramp function generator
Parameter overview
ID no.
Name
Range
min. ... max.
Unit
Standard
value
Display
only
velocity and ramp function generator
8228
set velocity value
-12000.0000 ... 12000.0000
rpm
0
(
)
8235
polarity of set velocity value
0
8230
positive velocity limit value
0.0000 ... 12000.0000
rpm
8231
negative velocity limit value
0.0000 ... 12000.0000
rpm
8283
bipolar velocity limit value
0.0000 ... 12000.0000
rpm
40
actual velocity value
-12000.0000 ... 12000.0000
rpm
41017
ramp function generator
0 ... 1
0
41018
ramp-up time
0.010 ... 60.000
s
0.01
41019
ramp-down time
0.010 ... 60.000
s
0.01
7.6.2 Rounding generator and torque
Parameter overview
ID no.
Name
Range
min. ... max.
Unit
Standard
value
Display
only
rounding generator and torque
41015
rounding generator
0 ... 1
0
41016
rounding generator time
10.0 ... 6000.0
ms
10
8272
set torque value for M control
-100.0 ... 100.0
%
0
8277
polarity of set torque value
0
8274
positive torque limit value
0.0 ... 100.0
%
100
(
)
8275
negative torque limit value
-100.0 ... 0
%
-100
(
)
8284
bipolar torque limit value
0.0 ... 100.0
%
100
(
)
84
actual torque value
-100.0 ... 100.0
%
Summary of Contents for BUS 6-T Series
Page 6: ...Abbreviations IV Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 10: ...Technical data 4 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 18: ...Assembly 12 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 22: ...Installation 16 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 40: ...Commissioning 34 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH ...
Page 52: ...Commissioning Torque control 46 Controller BUS 6 T 5 94017 06 Baumüller Nürnberg GmbH PC unit ...